HomeMy WebLinkAboutZP-24-274 - 0084 Ethan Allen Drive 9/16/2024
575 Dorset Street South Burlington, VT 05403 tel 802.846.4106 fax 802.846.4101 www.sburl.com
Conditions of Approval for #ZP-24-274
65 Ethan Allen Drive, Concrete Generator Pad
1. Per Article 13.12 (Utility Cabinets & Similar Structures) of the South Burlington Land
Development Regulations, “there shall be sufficient landscaping or fencing of sufficient height
and opacity to screen effectively the facility year-round from streets and abutting unaffiliated
properties”.
2. Submit the screening plan to the City’s Department of Planning & Zoning for review and
approval prior to installation.
As Noted
Sheet No:
Drawn By:
Scale:
-----
E-2
Date:7/22/24
ONE LINE DIAGRAM,
PANEL SCHEDULE
UVMHN CRITICAL CARE TRANSPORT
84 ETHAN ALLEN DR, SOUTH BURLINGTON, VT
SATELLITE FACILITY
DateRevision No.
N
ONE LINE DIAGRAM - EXISTING
N.T.S.
PROPOSED ELEVATION - PANEL P2
N.T.S.
EXISTING ELEVATION - PANEL P2
N.T.S.
8/16/24Misc. Revs.1
Diesel Product Line
JD40-03
40 kWe
208-600 Volt
60 Hz / 1800 RPM
Standby
Ratings
JD40-03 1 of 4
240V 208V 240V 480V 600V
Phase 1 3 3 3 3
PF 1.0 0.8 0.8 0.8 0.8
Hz 60 60 60 60 60
Generator Model UCI224D UCI224C UCI224C UCI224C UCI224C
Connection 12 LEAD DD 12 LEAD WYE 12 LEAD DELTA 12 LEAD WYE 4 LEAD WYE
kWe 40 40 40 40 40
AMPS 167 139 120 60 48
Temp Rise 125˚C / 40˚C 125˚C / 40˚C 125˚C / 40˚C 125˚C / 40˚C 125˚C / 40˚C
Engine
— Radiator Cooled Unit Mounted (50˚C)
— Radiator Duct Flange (OPU Only)
— Blower Fan & Fan Drive
— Starter & Alternator
— Oil Pump & Filter
— Oil Drain Extension w/Valve
— Governor - Electronic Isochronous
— 12V Battery System & Cables
— Air Cleaner (Dry Single Stage)
— Critical Grade Silencer Mounted
— Flexible Fuel Connector
— EPA Certified Tier 3
Generator
— Brushless Single Bearing
— Automatic Voltage Regulator
— ± 1% Voltage Regulation
— 4 Pole, Rotating Field
— 125˚C Standby Temperature Rise
— 100% of Rated Load - One Step
— 5% Maximum Harmonic Content
— NEMA MG 1, IEEE and ANSI
Standards Compliance for
Temperature Rise
Standard Equipment
Additional
— Single Source Supplier
— UL 2200 & cUL Listed
— CSA Certified
— Seismic Certified to IBC 2021
— NFPA 110 / CSA C282 Compliant
— Microprocessor Based Digital Control Panel
Mounted in NEMA 12 Enclosure
— Base - Formed Steel
— Main Line Circuit Breaker Mounted & Wired
— Battery Charger 12V 6 Amp
— Jacket Water Heater -20˚F 1500W 120V
w/Isolation Valves
— Vibration Isolation Mounts
— 2 Year / 2000 Hour Standby Warranty
— Standard Colors - White / Gray
Diesel Product Line
40 kWe
Application Data
JD40-03 2 of 4
Deration Factors: Rated Power is available up to 10,000 ft (3,048 m) at ambient temperatures to 122˚F (50˚C). Consult factory for site conditions above these parameters.
Engine
Manufacturer: John Deere Displacement - Cu. In. (lit): 275 (4.50)
Model: 4045TF280 Bore - in. (cm) x Stroke - in. (cm): 4.19 (10.6) x 5.00 (12.7)
Type: 4-Cycle Compression Ratio: 19.0:1
Aspiration: Turbo Charged Rated RPM: 1800
Cylinder Arrangement: 4 Cylinder Inline Max HP Stby (kWm): 75.0 (56.0)
Exhaust System Standby
Gas Temp. (Stack): °F (°C)945 (507)
Gas Volume at Stack Temp: CFM (m³/min)448 (12.7)
Maximum Allowable Exhaust Restriction in. H2O (kPa)30.0 (7.50)
Cooling System
Ambient Capacity of Radiator: °F (°C)122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H2O (kPa)0.50 (0.12)
Water Pump Flow Rate: GPM (lit/min)38.0 (144)
Heat Rejection to Coolant: BTUM (kW)1,821 (31.9)
Heat Radiated to Ambient: BTUM (kW)842 (14.7)
Air Requirements
Aspirating: CFM (m³/min)180 (5.09)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)4,760 (135)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)Consult Factory For Remote Cooled Applications
Fuel Consumption
At 100% of Power Rating: gal/hr (lit/hr)3.50 (13.2)
At 75% of Power Rating: gal/hr (lit/hr)2.76 (10.4)
At 50% of Power Rating: gal/hr (lit/hr)1.99 (7.53)
Fluids Capacity
Total Oil System: gal (lit)3.88 (14.7)
Engine Jacket Water Capacity: gal (lit)2.25 (8.52)
System Coolant Capacity: gal (lit)5.38 (20.4)
Diesel Product Line
40 kWe
JD40-03 3 of 4
Weights / Dimensions / Sound Data
80.00 38.00
6.00
16.55
25.58
51.05
19.58
(58.00)
2.00 (TYP.)
7.0118.01
5.38
10.38
25.58
2.00 (TYP.)
APPROX.BREAKERLOCATION
FUEL STUB-UPAREA 6 X 6
7.81 22.37
DCP7310 Control Panel
STOP STARTALARMAUTOMANUALOPTION
DIGITAL CONTROL PANEL
Menu Navigation
Module Display Four Configurable Status LEDs
Open Generator (Manual Mode Only)
Close Generator (Manual Mode Only)
Generator Available LEDGenerator Breaker LED
Stop / Reset Mode Button and Indicator Start Button
Alarm Mute & Lamp Test ButtonManual Mode Button and Indicator
Auto Mode Button and IndicatorConfigurable Button
Standard Features
— Digital Metering
— Engine Parameters
— Generator Protection Functions
— Engine Protection
— CAN Bus (J1939) ECU Communications
— Windows-Based Software
— Multilingual Capability
— Remote Communications to DSE2548 Remote Annunciator
— 8 Programmable Contact Inputs
— 10 Contact Outputs
— RS485 Communicator Interface
— cULus Listed, CE Approved
— Event Recording
— IP 65 rating (with supplied gasket) offers increased resistance to water ingress
— NFPA 110 Level 1 Compatible
L x W x H Weight lbs
OPU 80 x 38 x 58 in 2,100
Level 1 90 x 38 x 60 in 2,575
Level 2 90 x 38 x 60 in 2,625
Level 3 120 x 38 x 60 in 2,775
No Load Full Load
OPU 73 dBA 77 dBA
Level 1 71 dBA 73 dBA
Level 2 68 dBA 70 dBA
Level 3 63 dBA 65 dBA
Please allow 6-12 inches for height of exhaust stack.
Diesel Product Line
40 kWe
Enclosures & Fuel Tanks
JD40-03 4 of 4
60.00
38.00L
H
10.00
90.00
120.00
LE
V
E
L
3
E
N
C
L
O
S
U
R
E
24
/
4
8
H
R
72
H
R
Blue Star Power Systems, Inc.
2250 Carlson Drive
North Mankato, Minnesota 56003
Phone + 1 507 345 1776
bluestarps.com
quote.bluestarps.com
sales@bluestarps.com
— All enclosure models are 200 MPH wind rating certified in
accordance with IBC2021 and ASCE/SEI 7-16 standards.
— Level 2 & 3 enclosures include sound attenuation foam
— Level 3 enclosure includes frontal sound & exhaust hood.
— Enclosure height does not include exhaust stack.
Notes
— All specification sheet dimensions are represented in inches.
— All drawings based on standard 480 volt standby generator. Lengths may vary with
other voltages. All drawings and dimensions subject to change without notice.
— All enclosures and fuel tanks are based on the standard unit configuration. Any
requested deviation can change dimensions.
— Sound data is measured at 23 feet (7 meters) in accordance with ISO 8528-10.
— All materials and specifications subject to change without notice.
24 Hour 120 Gallon 48 Hour 240 Gallon 72 Hour 360 Gallon
L 80.00 80.00 108.00
H 80.00 96.00 96.00
As Noted
Sheet No:
Drawn By:
Scale:
-----
E-1
Date:7/22/24
EXISTING CONDITIONS
UVMHN CRITICAL CARE TRANSPORT
84 ETHAN ALLEN DR, SOUTH BURLINGTON, VT
SATELLITE FACILITY
DateRevision No.
N
OVERALL FLOOR PLAN
N.T.S.
8/16/24Misc. Revs.1
PROPOSED STAND-BY GENERATOR
(VIEW FROM STREET)
PROPOSED STAND-BY GENERATOR
(VIEW FROM NORTH SIDE LOOKING EAST)