HomeMy WebLinkAboutAgenda 06_SP-24-20_200 Davinci Dr_BSD Aviation Tech 180 Market Street, South Burlington, Vermont 05403 | 802-846-4106 | www.southburlingtonvt.gov TO: South Burlington Development Review Board FROM: Marla Keene, Development Review Planner SUBJECT: #SP-24-20 200 Davinci Drive DATE: June 18, 2024 Development Review Board meeting PROJECT DESCRIPTION Site plan application #SP-24-20 of Burlington School District to amend a previously approved plan for an airport complex. The amendment consists of renovating an existing hangar for the use of Burlington School District’s Aviation Technical Center, including reconfiguration of the parking and site circulation, 200 Davinci Drive. COMMENTS The Board reviewed this application on June 4, 2024. The Board continued the hearing for the purpose of allowing review of the revised materials submitted at the June 4 hearing date. This memo focuses on items for which no conclusion was reached on June 4, 2024, including discussion of the materials presented on that date. As always, the Board is welcome to bring up any concerns with the revised plans that are not highlighted herein. The Board is also reviewing the related master plan amendment at the June 18 hearing. A) SITE PLAN REVIEW STANDARDS 14.06 General Review Standards A. Relationship of Proposed Structures to the Site. (1) The site shall be planned to accomplish a desirable transition from structure to site, from structure to structure, and to provide for adequate planting, safe pedestrian movement, and adequate parking areas. The comment on this criterion in the June 4 Staff report focused on improving access to the site for users that are not arriving in cars or buses given the proposed use of the building for students, and the City’s prioritization of personal mobility (ie biking and walking). In response to the June 4 report, the applicant has added an on-grade striped walkway from the building across Davinci Drive to the existing sidewalk. Staff is strongly in support of a crossing of Davinci Drive but has concerns about the proposed crosswalk location relative to the 40-ft wide driveway that access both the proposed technical center and the Beta loading dock area, highlighted in pink below, as well as the location of the walkway relative to the driveway the applicant has testified is necessary for bus movements, highlighted in green below. #SP-24-20 2 1. Staff recommends the Board direct the applicant to relocate the crosswalk and walkway to a location that will provide safe pedestrian movement. 14.07 Specific Review Standards C. Access and Circulation. All proposed development shall comply with site access and circulation standards of Section 15.A.14. The applicant is proposing to modify the access and circulation in front of the existing hangars to the west of the subject building by formalizing one parking area, expanding another, and realigning and widening the driveway at the east end of the parking areas. They are not proposing modifications to the access and circulation in front of the subject building. Relevant standards of 15.A.14 include those pertaining to safe pedestrian access and to minimizing curb cuts by providing shared vehicular access. Davinci Drive is not currently a public street, but there is an irrevocable offer of dedication to the City therefore it should be treated as a public street for the purposes of layout and design. On June 4, the Board asked the applicant to demonstrate that the proposed pavement is minimized near the entrance to Davinci Drive, where there are four non-perpendicular vehicle movements proposed to occur. The applicant verbally stated that they have performed a turning movement analysis, but did not provide it. Members expressed interest in seeing that the pavement has been minimized. 2. Staff recommends the Board ask the applicant to provide a turning movement plan showing how the proposed configuration is optimized to minimize pavement and maximize pedestrian safety. H. Utility Services. Electric, telephone and other wire-served utility lines and service connections shall be underground insofar as feasible and subject to state public utilities regulations. Any utility installations remaining above ground shall be located so as to have a harmonious relation to neighboring properties and to the site. Standards of Section 15.A.18, Infrastructure, Utilities, and Services, shall also be met. #SP-24-20 3 The property is currently served by overhead utilities. The applicant testified that the utilities are underground from the utility pole near Davinci Drive to the building, and that it will remain so. Staff recommends the Board include a condition of approval requiring the line type on the plans to be updated to reflect that the utilities are underground. B) SUPPLEMENTAL REGULATIONS 13.02 Off Street Parking and Loading G. Design requirements for Parking Spaces, Parking Aisles, Lighting and Landscaping (1) Design requirements for off-street parking and loading are provided in Table 13-2 and Figure 13-1, Section 13.04, Landscaping , Screening, and Street Trees, and Section 13.07, Exterior Lighting. All paved parking spaces shall be striped or otherwise physically delimited. Sections 13.04 and 13.07 are discussed below. Parking is proposed to meet the required dimensional standards. (2) The location of parking areas and loading docks shall prevent conflicts with entering and existing traffic onto a public street and prevent conflicts between vehicles and pedestrians. The distance between access points and parking areas shall be adequate to minimize blockage and prevent back-ups onto the public street. Staff considers this criterion met. (3) Provision shall be made for access by police, fire and emergency vehicles. The Fire Marshal reviewed the project on 5/22/2024 and indicated there were no comments pertaining to the Development Review Board’s review of the project. (4) Pedestrian safety. Insofar as practicable, pedestrian and bicycle circulation shall be separated from motor vehicle circulation. Safe and convenient pedestrian circulation, including appropriate sidewalks, shall be provided on the site and its approaches. The pedestrian circulation on site shall be designed to minimize adverse effects of vehicular traffic on sidewalks and recreation paths. The applicant is proposing an on-grade striped pathway from the parking area to the building. On June 4, the applicant testified that they cannot provide a curbed sidewalk because the pavement needs to be flat in order to drain. Staff has reviewed the provided grading plans and watershed plans and is unable to reconcile the statement made by the applicant with the provided plans. It appears that if the sidewalk were raised, excess runoff from the pervious area north of the sidewalk would flow overland to the proposed bioretention area, and runoff from the proposed pavement would run along the curb to the proposed bioretention area. 3. Staff recommends the Board direct the applicant to raise the sidewalk so that it is protected from the drive aisle by curbing or in another manner. 13.03 Bicycle Parking and Storage. As discussed on June 4, the applicant is required to provide at least 5 short term bicycle parking spaces. The applicant testified that they are proposing 8 short term and 2 long term spaces. The required short term spaces are shown on the enlarged entrance plan, sheet SP-02. #SP-24-20 4 13.04 Landscaping, Screening & Street Trees B. Except for parking spaces accessory to a one-family or two-family dwelling, all off-street parking areas subject to review by the Development Review Board shall be curbed and landscaped with appropriate trees, shrubs, and other plants including ground covers, as approved by the Development Review Board. Sections of recessed curb are permitted if their purpose is to allow stormwater runoff from the adjacent parking area to reach stormwater collection, treatment and management infrastructure. The Development Review Board shall consider the adequacy of the proposed landscaping to assure the establishment of a safe, convenient, and attractive parking area and the privacy and comfort of abutting properties. The applicant is proposing to reconfigure and add parking so that there are 66 parking spaces west of the building. Staff considers these standards apply to those 66 spaces. (1) All off-street parking areas shall be landscaped around the perimeter of the lot with trees, shrubs and other plants. Perimeter planting shall be set back from the curb sufficiently to allow for snow storage. The purpose of perimeter planting shall be to mitigate the view of the parking lot from the public way and from adjacent uses and properties, and to provide shade and canopy for the parking lot. In some situations it may be necessary, both for surveillance purposes and for the perception of safety, to install the size and type of plants that leave visual access between the parking lot to the public way or other pedestrian areas. The applicant has provided a revised planting plan which includes six shrubs which reach a mature height of 2.5 feet, and 26 grasses, concentrated around the three northern most parking spaces. During the hearing the applicant indicated that the parking area is below the existing roadway. The plans indicate the parking area is approximately 4-feet below the existing roadway. Staff considers the grade difference to be sufficient to mitigate headlights from the adjoining roadway. The purpose of providing shade and canopy for the parking lot is not met. There are shade trees planted on the far side of Davinci Drive relative to the project, which Staff considers will not provide shade to the parking lot. Shade trees are specifically discussed under (4) below. (2) In all parking areas containing twenty-eight (28) or more contiguous parking spaces and/or in parking lots with more than a single circulation lane, at least ten percent (10%) of the interior of the parking lot shall be landscaped islands planted with trees, shrubs and other plants. Such requirement shall not apply to structured parking or below- ground parking. As discussed on June 4, this standard applies to this project and compliance is computed by taking the square footage of the parking area and the square footage of landscaping islands contained therein. Staff has estimated this to the best of their ability and calculates that roughly 8% of the interior of the parking lot consists of landscaping islands, though no trees are provided. 4. Staff recommends the Board direct the applicant to reduce the parking area, increase the landscaping area, or both, to meet this criterion, and demonstrate compliance by providing a figure. (3) All interior and perimeter planting shall be protected by curbing unless specifically designed as a collection and treatment area for management of stormwater runoff as per 13.04(B)(5)(c) below. Interior planted islands shall have a minimum dimension of six (6) #SP-24-20 5 feet on any one side, and shall have a minimum square footage of sixty (60) square feet. Large islands are encouraged. No curbing is shown on the proposed plans, though the applicant stated that they are proposing curbing on the Davinci Drive side of the parking lot. They note the presence of a stone lined swale along the airport side of the parking lot as a reason to not provide parking. Though Staff can confirm that stormwater runoff would indeed flow to that side of the parking lot based on the provided grading plan, the submitted plans only show a stone lined swale for approximately 16 feet of the 800+ foot long parking lot. 5. Staff recommends the Board require the applicant to provide curbing along the parking lot except for the 16-feet of stone line channel, and along the drive aisle where the drive aisle is adjacent to the bioretention area for protection of the plantings included therein, as well as along the Davinci Drive side of the parking lot. This recommendation is supported by the comments of the City stormwater section, below. (4) Landscaping Requirements (a) Landscaping shall include a variety of trees, shrubs, grasses and ground covers. All planting shall be species hardy for the region and, if located in areas receiving road runoff or salt spray, shall be salt-tolerant. This criterion should be used in designing the proposed landscaping for the revised and expanded parking lot. Staff recommends the Board seek the feedback of the City Arborist on the revised parking lot landscaping when provided. (b) At least one (1) major deciduous shade tree shall be provided within or near the perimeter of each parking area, for every five (5) parking spaces. The trees shall be placed evenly throughout the parking lot to provide shade and reduce glare. Trees shall be placed a minimum of thirty (30) feet apart. (c) Trees shall have a caliper equal to or greater than two and one-half (2 ½) inches when measured on the tree stem, six (6) inches above the root ball. (d) Where more than ten (10) trees are installed, a mix of species is encouraged; the species should be grouped or located in a manner that reinforces the design and layout of the parking lot and the site. As noted about, shading is the second purpose for requiring parking lot perimeter planting. The applicant testified that they cannot provide additional perimeter plantings due to grading. Staff has calculated that the slopes between the parking area and Davinci Drive range from 12% to 60%. 6. 14 shade trees would be required for 66 parking spaces. Staff recommends the Board direct the applicant to provide at least some fraction of the required shade trees. (7) Snow storage areas must be specified and located in an area that minimizes the potential for erosion and contaminated runoff into any adjacent or nearby surface waters. 7. Snow storage areas have been specified. These snow storage areas are located on slopes as steep as 60% upwards away from the pavement. Staff considers it unlikely that a snow plow would be able to push snow up a 60% slope and recommends the Board require the applicant to modify the snow storage areas to include areas that are actually realistic for snow storage. C. Screening or buffering. The Development Review Board will require landscaping, fencing, land shaping and/or screening along property boundaries (lot lines) whenever it determines that #SP-24-20 6 a) two adjacent sites are dissimilar and should be screened or buffered from each other, or b) a property’s appearance should be improved, which property is covered excessively with pavement or structures or is otherwise insufficiently landscaped, or c) a commercial, industrial, and multi- family use abuts a residential district or institutional use, or (d) a parking or loading area is adjacent to or visible from a public street. (1) There shall be sufficient landscaping, walls, or fencing of sufficient height (minimum of three (3) feet) and opacity to effectively screen the parking or loading area year-round from adjacent public streets. (2) Screening of a parking or loading shall be provided where headlights from vehicles on site may be visible and project parallel to a public street. Staff considers the elevation of the parking area relative to Davinici Drive to adequately meet these two criteria. I. Landscape Maintenance. Maintenance and responsibility. All planting shown on an approved site plan shall be maintained by the property owner in a vigorous growing condition throughout the duration of the use. Plants not so maintained shall be replaced with new plants at the beginning of the next immediately following growing season. Trees with a caliper of less than 5” may be replaced on an inch-by-inch basis with trees of the same genus of at least 2” caliper each. No permit shall be required for such replacements provided they conform to the approved site plan. Replacement of trees with a caliper of greater than 5” shall require an amendment to the site plan. The applicant is proposing to remove four (4) 8 to 10-inch caliper trees from the front of the building. The applicant is now proposing to plant thirteen shrubs and 68 ornamental grasses. 8. Staff considers the proposed plantings to be insufficient replacement for the removed trees, as they do not provide the same screening, shading, or general aesthetic value. Staff recommends the Board discuss with the applicant how they will compensate for the proposed tree removal. 13.05 Stormwater Management Stormwater standards apply when one-half acre or more of impervious surface exists or is proposed to exist, and where 5,000 sf of impervious is created or reconstructed. The City Stormwater Section reviewed the plans on June 11, 2024 and offers the following comments. The Stormwater Division has reviewed the BSD Aviation Technical Center Site Plan Application provided by EIV Technical Services. Please note that several issues were identified that, once remedied, may have resulting implications for the stormwater design’s compliance with the City’s LDRs and will likely require additional review. We would like to offer the following comments: 1. General Application Comments: a. Please provide a stormwater maintenance plan. b. If the applicant is proposing the use of site balancing to meet the requirements of the LDRs, please provide a narrative description of said site balancing. 2. HydroCAD Modeling: a. 1-year storm: Peak discharge at CB#2 under the proposed conditions exceeds the existing conditions peak discharge at CB#2. As per the LDRs Section 13.05.E.2, “The post-construction peak runoff rate for the one-year, twenty-four hour (rainfall amounts to be determined using NOAA, Atlas 14 data and a type II rainfall #SP-24-20 7 distribution) rain event shall not exceed the existing peak runoff rate for the same storm event from the site under conditions existing prior to submittal of an application.” Please revise design to comply with the LDRs. b. 25-year storm: Model indicates surcharging occurring at CB#2 under the proposed conditions. As per the LDRs Section 13.05.F.3, please revise design to ensure downstream structures retain capacity to convey the 25-year storm. c. The biorentention calls out a 1.0 in/hr discarded exfiltration, but also calls out 2.0 in/hr exfiltration routed to the outlet structure through an underdrain. Please provide justification for the discarded exfiltration modeling decision. d. Pre-treatment forebay: please provide sizing information for the forebay, ensuring that it meets the sizing requirements laid out in the Vermont Stormwater Management Manual (VSMM). 3. Sheet GR-01: a. Grading in the pervious (grassed) areas is inadequate to determine flow path of stormwater. Please provide details of how applicant will ensure all stormwater draining from the impervious area in Sub-catchment #2 will enter the bioretention via the pre-treatment forebay. b. Please provide information on how the applicant will prevent stormwater from creating a ponded area in the vicinity, both on and off the pavement, of the 312’ contour on the section of pavement connecting the two parking wings. Please note that there is an existing light pole to remain directly adjacent to this area. Grading information is inadequate to determine the extent of the ponding that may occur. c. Please indicate the elevation at the edge of the bioretention area on the plan. d. Staff recommends the applicant add curbing along the parking area to ensure all stormwater flows to the treatment area and enters via the pre-treatment forebay. 4. Sheet P-01: a. The delineation for Sub-catchment Area #2 does not appear to match the routing in the HydroCAD model. Please explain how runoff from the new impervious in the western corner of Sub-catchment Area #2 is being conveyed to the proposed bioretention area. b. Is site balancing being proposed to meet treatment requirements for the section of new impervious in Sub-catchment Area #1? If so, please indicate on the plan the size of the new area and the corresponding area in Sub-catchment Area #2 that will be used for site balancing. 5. Sheet MD-03: a. Please clarify the following in the bioretention basin detail: i. There is an underdrain shown, but the basin is called out as an “infiltration basin”. Please clarify whether or not this is an infiltrating bioretention practice. ii. The “Temporary/Permanent Sediment Forebay/Basin” callout. Please clarify which of these options is shown here. iii. Please clarify whether or not the outlet structure is meant to comply with the “Drainage Structure” detail on this same sheet. If not, please provide details of the outlet structure. #SP-24-20 8 6. EPSC: Please consider using the footprint of the bioretention area as a temporary sediment basin during construction. 9. Because of the extensive nature of the comments of the City Stormwater Section, Staff recommends the Board continue the hearing to allow these comments to be addressed. 13.07 Exterior Lighting Lighting requirements are summarized as follows. (1) Fixtures must be downcast and shielded (2) Illumination must be evenly distributed (3) Fixtures must be placed to minimize lighting from becoming a nuisance (4) Poles shall be rustproof metal, cast iron, fiberglass, finished wood or similar structural material, with a decorative surface or finish (5) Poles & building mounted fixtures may be no higher than 30-ft (6) Poles must be located in safe locations Specific requirements for maximum illumination levels are included in Appendix A and are limited to 3-foot candles average at ground level. The applicant has provided a photometric drawing but has not indicated an average illumination level, though Staff considers it is likely to be below 3 foot candles. The applicant has modified the previously submitted plan to remove the “hotspot” of 15 footcandles near the eastern entrance of the building. Illumination levels are now no greater than 9 footcandles. Staff considers lighting requirements to be met. 13.12 Utility Cabinets and Similar Structures B. Specific Standards for Utility Cabinets and Similar Structures. (4) There shall be sufficient landscaping or fencing of sufficient height and opacity to screen effectively the facility year-round from streets and abutting unaffiliated properties. 10. The applicant testified that the generator is proposed to be 8 – 9 ft high, and the transformer is 5 – 6 ft high. The applicant further testified that the proposed plantings will only partially screen the equipment. Staff recommends the Board require the applicant to provide screening of sufficient height to screen the transformer from the street. (5) The location of the facility shall be shown on all relevant site plans. (6) Utility cabinets and similar structures shall be located a minimum of five (5) feet from all existing or planned public roads or rights-of-way. Staff considers criterion #5 and 6 to be met. RECOMMENDATION Staff recommends that the Board work with the applicant to address the issues identified herein. S S D D D D D D D 8" ø G T S 8" ø G T R 4"PO P L A R ( 2 ) VEN T P I P E 14"M A P L E CO N C . W A L K GATE 10"A P P L E 11 23 21 EXISTING HANGER BUILDING EXISTING HANGER BUILDING EXISTING HANGER BUILDING PROPOSED BSD AVIATION TECHNICAL CENTER (REHABILITATION OF EXISTING HANGER BUILDING) EXISTING VERMONT FLIGHT ACADEMY BUILDING BETA TECHNOLOGIES BUILDING EXISTING APRON TO REMAIN UE 2 4 ' 207' 198' 200' 15 ' 2' 24' 13.37 ' 1 1 . 2 2 ' R10' R5' R5' R3' R10' 9' 1 2 . 1 ' R5' R3'R38'R5' R5' ±75' RELOCATED SECURITY FENCE 50'± RETAINING WALL (HIGHEST WALL HEIGHT=±2') RECONFIGURE/EXPAND PARKING 66 SPACES (26 NET INCREASE) STRIPED ADA COMPLIANT PEDESTRIAN WALKWAY EXISTING RETENTION BASIN RELOCATED FIRE HYDRANT EXISTING OVERHEAD DOOR TYP. BETA LIGHT POLE, TYP. BETA LEASE LINE PROPOSED BIORETENTION AREA EXISTING ASPHALT PAVEMENT TO BE REHABILITATED (20,084 SF) PROPOSED FULL DEPTH ASPHALT PAVEMENT (7778 SF) PROPOSED CONCRETE PAD EXPANSION (2.8'x6.3') PROPOSED CONCRETE SIDEWALK (34.5'x4.1') 64.79' 64.79'47.91' 30.67' VERMONT FLIGHT ACADEMY LEASE LINE RELOCATED GATE CARD READER 7 4 ' R62' RIP RAP CHANNEL LINING EXISTING SECURITY FENCE & GATE TO REMAIN SEE SHEET SP-02 FOR DETAILED VIEW PROPOSED CONCRETE HVAC EQUIPMENT PAD (24' X 5') .32' PROPOSED OVERHEAD DOOR PROPOSED GENERATOR PAD PROPOSED TRANSFORMER PAD PROPOSED LAWN AREA ADA PARKING SIGNS MOUNTED ON EXISTING SECURITY FENCE PROPOSED LANDSCAPING AREAMAIN ENTRANCE EXISTING HANGER DOOR TO REMAIN EXISTING DUMPSTER, COMPOSTING, RECYCLING AREA PROPOSED SNOW STORAGE AREA PROPOSED SNOW STORAGE AREA PROPOSED SNOW STORAGE AREA 9' TYP. 18' TYP. 24' TYP. 5' R49' R164.5' MUTCD W11-2 (30" x 30") TYP. OF 4 PROPOSED SIDEWALK RAMP 22 12 CL I E N T : PR O J E C T : K: \ B U R L I N G T O N I N T E R N A T I O N A L A I R P O R T \ T - 1 8 7 1 5 . 0 2 A V I A T I O N T E C H N I C A L D E S I G N \ D R A W \ D R A W I N G S \ S H E E T F I L E S \ 1 8 7 1 5 . 0 2 - L A Y O . D W G NOT FOR CONSTRUCTION 426 INDUSTRIAL AVENUE, SUITE 146 WILLISTON, VT 05495 P: (802)862-9381 WWW.MJINC.COM 81 Maple Street▪ Burlington VT 05401 802▪864▪6844▪ www.fffinc.com Architecture▪ Planning▪ Interiors BU R L I N G T O N A V I A T I O N T E C H N I C A L C E N T E R 20 0 D A V I N C I D R I V E , S O U T H B U R L I N G T O N , V T 0 5 4 0 3 BU R L I N G T O N S C H O O L D I S T R I C T BU R L I N G T O N , V E R M O N T SCALE 0 20 40 60 FT LEGEND PROPOSED HYDRANT LEASE LINES PROPOSED PAVEMENT REHABILITATION PROPOSED FULL DEPTH PAVEMENT PROPOSED LAWN AREA'S PROPOSED PEDESTRIAN WALKWAY CONCRETE PADS MANDOOR OVERHEAD DOOR SITE PLAN 1"=20' JES AJF AJF 18715.02 03/01/2024 SP-01 PERMIT SET PROJECT DATA 1. APPLICANT / LAND OWNER: BURLINGTON SCHOOL DISTRICT 200 DAVINCI DRIVE SOUTH BURLINGTON, VERMONT 05403 2.EXISTING ZONING: AIRPORT INDUSTRIAL PARKING: 1 SPACE FOR EACH 2 EMPLOYEES ON MAXIMUM WORKING SHIFT. TOTAL EMPLOYEES = 10 REQUIRED: 5 TOTAL SPACES REQUIRED PROVIDED: 12 (UNSHARED), 79 TOTAL SPACES ADA SPACES REQUIRED: PER 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN REQUIRED (75-100 SPACE LOT): 4 SPACES) FOR TOTAL PARKING 50-100 SPACES PROVIDED (79 SPACE LOT): 4 SPACES ZONING: EXISTING:±796 ACRES AIRPORT INDUSTRIAL PROPOSED:±796 ACRES AIRPORT INDUSTRIAL TAX ACCOUNT NUMBERS:600-188-10911 SITE DATA FEATURE REQUIRED PROPOSED MINIMUM LOT SIZE, NONRESIDENTIAL 3 ACRES 796.05 ACRES MINIMUM FRONT YARD, FROM RIGHT-OF-WAY 50 FEET > 50 FT MINIMUM SIDE YARD 35 FEET > 35 FEET MINIMUM REAR YARD 50 FEET > 50 FEET MAXIMUM HEIGHT 40 FEET N/A MAXIMUM LOT COVERAGE 50%N/A 1 4/10/2024 CITY COMMENTS 2 5/31/2024 CITY COMMENTS S S DD D FD FDFDFDFDFD FD FD FD FD FD FD FD FD FD FD FDFDFDFD D D D FD FD FD FD FDFD FD FDFDFD 8" ø G T S 8" ø G T R VEN T P I P E 14"M A P L E FM FM FM FM FM F M F M F M FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM GATE 10"A P P L E W W G G G UE EXISTING UTILITY POLE TO REMAIN EXISTING UTILITY POLE TO REMAIN EXISTING STORM CATCH BASIN TO REMAIN EXISTING STORM CATCH BASIN TO REMAIN EXISTING BIO EXISTING HANGER BUILDING EXISTING HANGER BUILDING EXISTING HANGER BUILDING PROPOSED BSD AVIATION TECHNICAL CENTER (REHABILITATION OF EXISTING HANGER BUILDING) BETA TECHNOLOGIES BUILDING X2 X2 X2 X2 X1 (2) X2 X2 EXISTING BETA SITE LIGHT POLE, TYP. PROPOSED LANDSCAPING BED PROPOSED LAWN AREA CS 2CS 5 BG 9 SC 32 X2 X3 X3 CS 6 BG 11 SC 15 BG 5 SC 14 CL I E N T : PR O J E C T : DRAWN DESIGNED CHECKED SCALE DATE PROJECT NO.DATE DESCRIPTION DRAWING TITLE DRAWING NUMBER PROJECT MILESTONE K: \ B U R L I N G T O N I N T E R N A T I O N A L A I R P O R T \ T - 1 8 7 1 5 . 0 2 A V I A T I O N T E C H N I C A L D E S I G N \ D R A W \ D R A W I N G S \ S H E E T F I L E S \ 1 8 7 1 5 . 0 2 - L I G H T I N G . D W G NOT FOR CONSTRUCTION 426 INDUSTRIAL AVENUE, SUITE 146 WILLISTON, VT 05495 P: (802)862-9381 WWW.MJINC.COM 81 Maple Street▪ Burlington VT 05401 802▪864▪6844▪ www.fffinc.com Architecture▪ Planning▪ Interiors BU R L I N G T O N A V I A T I O N T E C H N I C A L C E N T E R 20 0 D A V I N C I D R I V E , S O U T H B U R L I N G T O N , V T 0 5 4 0 3 BU R L I N G T O N S C H O O L D I S T R I C T BU R L I N G T O N , V E R M O N T SCALE 0 20 40 60 FT LEGEND EXISTING SITE LIGHT POLES PROPOSED BUILDING MOUNTED LIGHTS PROPOSED PLANTINGS X2 SC 3 LIGHTING & LANDSCAPING PLAN 1"=20' DEL AJF AJF 18715.02 03/01/2024 LL-02 PERMIT SET PLANTING NOTES 1.ALL NEW PLANT MATERIAL SHALL CONFORM TO THE MINIMAL GUIDELINES ESTABLISHED BY THE AMERICAN STANDARD FOR NURSERY STOCK PUBLISHED BY THE AMERICAN ASSOCIATION OF NURSERYMEN, INC. PROVIDE QUALITY, SIZE, GENUS, SPECIES, VARIETY OF TREES AND SHRUBS INDICATED, AND ROOT BALL SIZE COMPLYING WITH APPLICABLE REQUIREMENTS OF ANSI Z60.1 “AMERICAN STANDARD FOR NURSERY STOCK.” ALL PLANTS SHOULD BE NURSERY GROWN UNDER CLIMATIC CONDITIONS SIMILAR TO THOSE IN THE LOCALITY OF THE PROJECT. 2.PLANT SIZES: MEASURE TREES AND SHRUBS ACCORDING TO ANSI Z60.1 WITH BRANCHES AND TRUNKS OR CANES IN THEIR NORMAL POSITION. TAKE CALIPER MEASUREMENTS 6 INCHES ABOVE GROUND FOR TREES UP TO 4-INCH CALIPER SIZE, MEASURE MAIN BODY OF TREE OR SHRUB FOR HEIGHT AND SPREAD; DO NOT MEASURE BRANCHES OR ROOTS TIP-TO-TIP. 3.ALL CONTAINER GROWN PLANTS SHALL SIZED ACCORDING TO ANSI Z60.1 FOR TYPE AND SIZE OF PLANT REQUIRED. PLANTS SHALL BE PREMIUM QUALITY, APPEAR 'FULL', OR 'HEAVY' WITHIN THEIR CONTAINER, AND BE REPRESENTATIVE OF THE CONTAINER SIZE SPECIFIED. PLANTS DEEMED TO BE SUBSTANDARD IN SIZE BY THE OWNERS REPRESENTATIVE WILL BE REJECTED. 4.ALL NEW PLANTS TO BE BALLED AND BURLAPPED OR CONTAINER GROWN UNLESS OTHERWISE NOTED ON PLANT LIST. 5.TREES SHOULD BE FRESHLY DUG DURING THE SEASON OF PLANTING, MARCH 1ST TO MAY 1ST FOR SPRING PLANTING AND OCTOBER 15TH TO DECEMBER 15TH FOR FALL PLANTING. PLANTS KNOWN AS FALL DIG HAZARDS SHALL BE DUG IN THE SPRING ONLY. 6.THE CONTRACTOR SHALL SUPPLY ALL NEW PLANT MATERIAL IN QUANTITIES SUFFICIENT TO COMPLETE THE PLANTING SHOWN ON THE DRAWINGS. 7.IN GENERAL, PLANT SPECIES SUBSTITUTIONS WILL NOT BE ACCEPTED. IF SPECIFIED MATERIAL IS NOT OBTAINABLE, CONTRACTOR SHALL SUBMIT PROOF OF NON-AVAILABILITY ALONG WITH PROPOSED SUBSTITUTION. ANY PROPOSED SUBSTITUTIONS OF PLANT SPECIES SHALL BE MADE WITH PLANTS OF EQUIVALENT OVERALL FORM, HEIGHT, SIZE, BRANCHING HABIT, FLOWER, LEAF, COLOR, FRUIT AND CULTURE, AND ONLY AFTER WRITTEN APPROVAL OF THE OWNERS REPRESENTATIVE. 8.THE OWNERS REPRESENTATIVE RETAINS THE RIGHT TO INSPECT TREES AND SHRUBS FOR SIZE AND CONDITION OF BALLS AND ROOT SYSTEMS, INSECTS, INJURIES AND LATENT DEFECTS, AND TO REJECT UNSATISFACTORY OR DEFECTIVE MATERIAL AT ANY TIME DURING PROGRESS OF WORK. CONTRACTOR SHALL REMOVE REJECTED TREES OR SHRUBS IMMEDIATELY FROM PROJECT SITE. 9.CONTRACTOR SHALL LOCATE AND VERIFY ALL EXISTING UTILITY LINES PRIOR TO PLANTING AND SHALL REPORT ANY CONFLICTS TO THE OWNERS REPRESENTATIVE. 10.INSTALLED PLANTS SHALL BEAR THE SAME RELATIONSHIP TO PROPOSED GRADE AS THEY BORE TO PREVIOUS GRADE. NO TREES SHALL BE PLANTED BEFORE ACCEPTANCE OF ROUGH GRADING. 11.CONTRACTOR SHALL PROVIDE LONG LASTING, SLOW RELEASE STARTER FERTILIZER IN EACH PLANTING PIT FOR TREES, SHRUBS AND PERENNIALS. 12.ALL PLANT BEDS SHALL RECEIVE THREE INCHES (3") OF SHREDDED BARK MULCH. MULCH SHALL BE FREE FROM DELETERIOUS MATERIALS AND SUITABLE AS A TOP DRESSING OF TREES AND SHRUBS, CONSISTING OF DOUBLE HAMMERED SHREDDED BARK MULCH COMPRISED OF EITHER HARDWOOD OR SOFTWOOD SHREDDED BARK. SHREDDED BARK MULCH SHALL NOT EXCEED 3" IN GREATEST DIMENSION, AND SHALL BE DARK BROWN IN COLOR. 13.PLANTS SHALL BE DELIVERED ONLY AS THEY CAN BE INSTALLED IN REASONABLE TIME. ALL PLANTS ARE SUBJECTED TO INSPECTION AT DELIVERY BY THE OWNER'S REPRESENTATIVE. 14.IF DISCREPANCIES EXIST BETWEEN THE NUMBER OF PLANTS DRAWN ON THE PLANTING PLAN AND THE NUMBER OF PLANTS IN THE PLANT LIST, THE PLANTING PLAN SHALL GOVERN. 15.MAINTENANCE SHALL BEGIN IMMEDIATELY AFTER EACH PLANT IS PLANTED AND SHALL CONTINUE FOR A MINIMUM 30-DAY MONITORING PERIOD AFTER NOTIFICATION OF SUBSTANTIAL COMPLETION OF PLANTING, AND UNTIL FINAL ACCEPTANCE. MAINTENANCE INCLUDES PRUNING, WEEDING, WATERING, FERTILIZATION, AND RE-SEEDING AS NECESSARY. 16.PROTECT PLANTS FROM DAMAGE DUE TO LANDSCAPE OPERATIONS AND OPERATIONS OF OTHER CONTRACTORS AND TRADES. MAINTAIN PROTECTION DURING INSTALLATION AND MAINTENANCE PERIODS. TREAT, REPAIR, OR REPLACE DAMAGED PLANTINGS. 17.ACCEPTANCE STANDARDS: 17.1.PLANTS SHALL BE FREE OF FROST CRACKS; SUN SCALD; DAMAGE DUE TO INSECTS, PESTS, AND DISEASE; STRUCTURAL DEFECTS; AND DAMAGE RESULTING FROM MACHINERY OR TOOLS. ALL PLANTS REGARDLESS OF THE SEASON OF REVIEW SHALL HAVE A MINIMUM OF 75 PERCENT HEALTHY, BALANCED BRANCHING STRUCTURE WITH A HEALTHY TERMINAL LEADER(S) WITH VIABLE TERMINAL BUD(S). TREES SHALL BE PLUMB AND SHOW NO SIGNS OF UNEVEN SETTLING OR LEANING. 17.2.LAWN AREAS SHALL HAVE A HEALTHY, UNIFORM STAND OF GRASS FREE OF WEEDS, SURFACE IRREGULARITIES, WITH COVERAGE EXCEEDING 90% OVER ANY 10 SQ. FT. AND BARE SPOTS NOT EXCEEDING 5"X5" 18.CONTRACTOR SHALL REPLACE ALL PLANTS THAT ARE MORE THAN 25% DEAD OR, AS DETERMINED BY THE OWNERS REPRESENTATIVE, ARE IN AN UNHEALTHY OR UNSIGHTLY CONDITION. CONTRACTOR SHALL BEAR THE COST OF COMPLETE REPLACEMENT(S). REPLACEMENTS SHALL BE OF THE SAME SIZE AND SPECIES AS SPECIFIED ON THE PLANTING LIST. 19.GUARANTEE: CONTRACTOR SHALL GUARANTEE ALL PLANT MATERIAL TO REMAIN ALIVE AND BE IN A HEALTHY, VIGOROUS CONDITION FOR A PERIOD OF ONE YEAR AFTER FINAL ACCEPTANCE OF PLANTING WORK, AGAINST DEFECTS INCLUDING DEATH AND UNSATISFACTORY WORK. 20.GRASS SEED SHALL BE FRESH, CLEAN, DRY, NEW-CROP SEED COMPLYING WITH AOSA'S "RULES FOR TESTING SEEDS" FOR PURITY AND GERMINATION TOLERANCES. PROVIDE SEED MIXTURE COMPOSED OF SPECIES, PROPORTIONS AND MINIMUM PERCENTAGES OF PURITY, GERMINATION, AND MAXIMUM PERCENTAGE OF WEED SEED, AS FOLLOWS: PROPORTION GERMINATION PURITY COMMON NAME BY WEIGHT MINIMUM MINIMUM CREEPING RED FESCUE 50% 85%95% OR CHEWINGS FESCUE KENTUCKY BLUEGRASS 25% 85% 90% PERENNIAL RYE 25%90%90% 21.PLANTING SOIL & TOPSOIL SHALL HAVE A SANDY LOAM, LOAMY SAND, OR LOAM TEXTURE AS DETERMINED BY MECHANICAL ANALYSIS (ASTM 422) AND BASED ON THE 'USDA CLASSIFICATION SYSTEM' MAXIMUM CLAY CONTENT SHALL BE 10%. TOPSOIL SHALL BE FERTILE, FRIABLE SOIL FREE OF STONES LARGER THAN ONE INCH IN ANY DIRECTION, LUMPS, PLANTS AND THEIR ROOTS, DEBRIS AND OTHER EXTRANEOUS MATTER AS DETERMINED BY THE OWNER'S REPRESENTATIVE, AND TOXIC MATTER HARMFUL TO PLANT GROWTH, PLANTING SOIL /TOPSOIL SPECIFICATION: GRADATION: SIEVE % PASSING BY WEIGHT CHEMICAL ANALYSIS MIN. MAX. #10 100 PH RANGE 5.2-7.0 #20 78 95 ORGANIC MATTER 4%-6% #40 67 87 MAGNESIUM 35LB. PER AC #60 48 78 PHOSPHORUS 75LB/AC #100 40 75 POTASSIUM 85LB/AC #200 28 63 SOLUBLE SALTS NOT TO EXCEED 500 #270 22 55 PPM .002 2 7 PLANTING SCHEDULE: SYM.QTY.BOTANICAL NAME COMMON NAME SIZE REMARKS/SPACING SHRUBS CS 13 Cornus sericea 'Artic Fire'DWARF RED TWIG DOGWOOD #3 3' O.C. ORNAMENTAL GRASS BG 25 Bouteloua gracilis 'Blonde Ambition'BLUE GRAMA GRASS PLUGS 24" O.C. SC 61 Schizachyrium scoparium 'Blaze'LITTLE BLUESTEM PUGS 18" O.C. 1 SHRUB PLANTING SCALE: NTS 2 GRASS PLANTING SCALE: NTS SPACE SHRUBS AS INDICATED ON PLANS 3" BARK MULCH SET CROWN FLUSH WITH TOP OF MULCH PLANT GRASSES IN CONTINUOUS BED OF SPECIFIED PLANTING SOIL COMPACTED / UNDISTURBED SUBGRADE 3" DEPTH SHREDDED BARK MULCH; PULL AWAY FROM ROOT FLARE. CUT AND REMOVE BURLAP FROM TOP 1/3 OF ROOT BALL PLANT SHRUBS IN CONTINUOUS BED OF SPECIFIED PLANTING SOIL UNDISTURBED SUBGRADE ROOT FLARE SHALL BEAR SAME RELATIONSHIP TO FINISH GRADE AS IT BORE TO PREVIOUS EXISTING GRADE 12" MIN18 " M I N 6" MIN 12 " M I N 1. PROVIDE INTEGRAL EMERGENCY BATTERY (14 WATT OR SIMILAR) FOR ALL FIXTURES WITH "E" EMERGENCY DESIGNATION NOTES: LIGHT FIXTURE SCHEDULE TYPE MARK DESCRIPTION WATTS (W)MANUFACTURER MODEL VOLTAGE MOUNTING SWITCH ID COMMENTS X1 SURE-LITES EUX SERIES UNIVERSAL MOUNT 11 COOPER LIGHTING EUX7-1-R-WH MVOLT SURFACE AND WALL X2 Wavestream and 1-2 Light Squares 32 COOPER LIGHTING CCW LED UNV.SURFACE AND WALL X3 Wavestream and 1-2 Light Squares 32 COOPER LIGHTING CCW LED UNV.SURFACE AND WALL 2 5/31/2024 CITY COMMENTS 2 2 2 355 Main Street | Suite 500 | Winooski, VT 05404 | w. eivtech.com May 31, 2024 Marla Keene, PE Development Review Planner City of South Burlington 180 Market Street South Burlington, VT 05403 Re: Burlington International Airport Burlington School District’s Aviation Technical Center Project Site Plan Application Response to Staff Comments for DRB 6/4/2024 Dear Marla Keene, Thank you for your time to review our site plan application for the above reference project. In advance of the Development Review Board meeting on June 4, 2024, we are providing a response to staff comments. Two plansheets have been revised and resubmitted in response to these comments. These plansheets have cloud revision bubbles around the proposed changes. The appropriate file naming convention (noting the revision date in the file name) has been made and they have been uploaded to the ShareFile Site Plan Application submission folder. The revised plansheets are referenced in the the response to comments below: 1. There is no safe pedestrian access to the building from Davinci Drive either existing or proposed, though there is a sidewalk along Davinci Drive. Given the proposed use of the building for students, and the City’s prioritization of personal mobility (ie biking and walking), Staff recommends the Board discuss with the applicant how to improve access to the site for users that are not arriving in cars or buses. Response: A walkway and crosswalk with signage have been added to the site plan (06_SP-01 - SITE PLANS_REV20240531) to provide the requested pedestrian access from the recently constructed Da Vinci Drive sidewalk. 2. Staff recommends the Board ask the applicant to demonstrate that the parking is the minimum necessary and discuss whether they will allow this exemption for parking. Response: The net increase in parking of 26 spaces is the minimum necessary for the school’s proposed operations. 355 Main Street | Suite 500 | Winooski, VT 05404 | w. eivtech.com 3. Staff recommends the Board ask the applicant to demonstrate that the proposed pavement is minimized near the entrance to Davinci Drive. Too wide open a pavement area with multiple (four in this case) non-perpendicular locations for cars to come from can lead to safety issues. The driveway at the west end is narrow, so it does not appear this area is needed for large vehicle circulation. Response: The pavement width in this area is necessary for the operations of the Beta loading docks. This is an existing condition as that entrance was just paved last year as part of the Beta assembly plant project. This widened pavement is also necessary for the school buses to make their turn movement from the bus loading area onto Da Vinci Drive. 4. Staff recommends the Board ask the applicant to explain at what point the existing overhead utilities will be located underground, and consider requiring the utilities to be located underground at the upstream most pole that is impacted by the work. Response: The existing power service to the building is currently underground from the adjacent transformer and this transformer is powered via underground conduits to the pole near Da Vinci Drive. With the installation of a new transformer this same underground configuration is being proposed as shown on the Utility Site Plan. 5. Staff recommends the Board ask the applicant to verbally answer the questions of the Director of Public Works and include conditions for any necessary modifications. ●The applicant will need to work with the wastewater superintendent to confirm that the project has a sufficient wastewater allocation for the change in use. Response: A coordination meeting was held with the water & sewer department after the submission of our Water & Sewer Engineers report to the City, which resulted in the issuance of an Ability To Serve letter by the water district and verbal concurrence for wastewater. The Ability To Serve letteris included in our application. ●The wastewater pump station will remain privately owned. Response: Correct ●Does the property have an existing oil / water / grease / grit separator? Will the change in use require that one be installed? Response: An existing oil/water separator exists for the current floor drains and will be rehabilitated or replaced as part of the proposed project. The proposed kitchenette area will be for warming food only, and no food preparation will occur onsite. Therefore a grease trap is not required. ●Are any water (or other) easements proposed to be transferred to the City? Response: No 6. The applicant is proposing an on-grade striped pathway from the parking area to the building. Staff recommends the Board consider requiring the pathway to be raised by a curb and consider requiring a sidewalk connection and crosswalk to Davinci Drive, as alluded to above. Response: See response to #1 above. A raised walkway was not proposed as stormwater runoff from traverses across the pavement to the existing closed drainage systems. 355 Main Street | Suite 500 | Winooski, VT 05404 | w. eivtech.com 7. The building is 34,445 sf and is proposed to be used by 12 employees and 100 students. One short term space is required for each 20 students of planned capacity, or five spaces. It does not appear the applicant has proposed any bicycle parking. Staff recommends the Board require the applicant to add short term bicycle parking to the plan proximate to a student entrance. Response: The project is proposing 8 bike spaces as shown on drawing SP-02. These are covered spaces with a bike rack. The project is also planning for 2 interior bike lockers as well. 8. No parking lot landscaping is proposed. Staff recommends the Board require the applicant to revise their plans to provide landscaping to screen the proposed and reconfigured parking from the future public street. Response: The landscaping plan, drawing LL-02 (14_LL-02 - LIGHTING & LANDSCAPING PLAN_REV 20240531) has been revised to include additional plantings around the existing parking lot that will be expanded. The locations for proposed plantings are limited due to the slopes between DaVinci Drive and the parking area. 9. Staff recommends the Board require the applicant to demonstrate compliance with this criterion by providing a figure showing the parking area and the fraction landscaped. (2) In all parking areas containing twenty-eight (28) or more contiguous parking spaces and/or in parking lots with more than a single circulation lane, at least ten percent (10%) of the interior of the parking lot shall be landscaped islands planted with trees, shrubs and other plants. Such requirement shall not apply to structured parking or below ground parking. Response: Although the parking area has more than 28 spaces, it is a single drive isle with no opportunities for internal landscape areas. In response to these comments, additional landscaping is proposed around the parking lot as described in the response to #8 above. 10. No curbing is proposed. Staff considers curbing will be required to protect adjacent landscaping except where the adjacent area is specifically designed as a stormwater collection or treatment area. Response: Curbing is proposed along the frontage of the building as well as on the Da Vinci Road side of the parking lot expansion area. Curbing is intentionally not proposed between the proposed work area and the GA Hangar pavement areas because it would restrict the current stormwater runoff from this area into the existing closed drainage system. The proposed work includes a stone line channel to direct the runoff to the proposed bioretention basin for treatment prior to entering the existing drainage system. 11. While Staff considers the proposed plantings to not be sufficient replacement for the removed trees, as described above, the applicant must also provide parking lot landscaping, including shade trees. Staff considers the combined resulting planting likely to be adequate to replace the removed trees, and recommends the Board confirm once the proposed parking lot planting plan is complete. Response: Additional plantings have been added, please refer to the response to #8 above. 355 Main Street | Suite 500 | Winooski, VT 05404 | w. eivtech.com 12. Staff recommends the Board provide Staff an opportunity to provide an update at the time of the hearing. (related to any stormwater comments, none received to date) Response: No response required at this time, we had a pre-application meeting with the stormwater department and can answer any additional comments they may have. 13. Staff recommends the Board require the applicant to demonstrate submission of an application for Determination of No Hazard, and condition the approval on receipt of an issued determination. (Development within the Airport Approach Cones) Response: This is not applicable as it is only required for new or expanded buildings. This is an existing buildings and submission of a FAA 7460 airspace analysis review is not required. 14. Staff notes there is one “hotspot” of 15 footcandles near the eastern entrance of the building and recommends the Board discuss whether to direct the applicant to reconfigure the proposed lighting to reduce this hotspot to on the order of 8 – 10 footcandles. Response: This is the result of three closely spaced man doors with lights over each door, the center man door light has been removed to reduce the light intensity in this isolated area to less than 10 footcandles. Please see the revised drawing LL-02 (14_LL-02 - LIGHTING & LANDSCAPING PLAN_REV 20240531). 15. Screening is proposed for the proposed generator but not for the proposed utility transformer. Staff recommends the Board ask the applicant to describe the proposed height of the generator in order to determine if screening is adequate. Response: At this time the generator is expected to be roughly 8-9’ in height based on preliminary sizing. The proposed plantings will partially screen the generator. 16. Staff recommends the Board require the applicant to provide screening of sufficient height to screen the transformer from the street. Response: Additional plantings have been added between the transformer and the sidewalk as screening as shown on the revised drawing LL-02 (14_LL-02 - LIGHTING & LANDSCAPING PLAN_REV 20240531). We would propose grasses similar to what is proposed in front of the generator. These would provide a partial screening to the height of the transform (estimated to be 5-6’ in height) but would also still allow access to the transformer for maintenance & inspections. We appreciate your time to review and receive our response to staff comments in advance of the Development Review Board meeting on June 4, 2024. Feel free to contact Larry Lackey, or Jacqueline Dagesse at EIV, with any questions regarding this submission, 802-324-5522. Very Respectfully, EIV Technical Services Jacqueline Dagesse, MBA, CPESC President / Environmental Engineer E PAVEME N T J O I N T PAVEMENT J O I N T 36"CMP 19-1 19-1 19-1 19-1 19-1 19- 1 19-1 19-1 19- 1 E R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A RSA R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A R S A RSA R S A R S A R S A R S A R S A R S A R S A R S A R S A TS A TS A TO F A TO F A LAT:N044° 28' 50" LONG:W073° 09' 57" LAT:N044° 27' 57" LONG:W073° 08' 30" LAT:N044° 28' 30" LONG:W073° 09' 12" LAT:N044° 27' 50" LONG:W073° 09' 04" LAT:N044° 28' 50" LONG:W073° 09' 57" LAT:N044° 27' 57" LONG:W073° 08' 30" LAT:N044° 27' 50" LONG:W073° 09' 04" LAT:N044° 27' 50" LONG:W073° 09' 04" LAT:N044° 28' 50" LONG:W073° 09' 57" LAT:N044° 27' 57" LONG:W073° 08' 30" LAT:N044° 28' 30" LONG:W073° 09' 12" LAT:N044° 27' 50" LONG:W073° 09' 04" TO F A TO F A RO F A / R O F Z RO F A / R O F Z RO F A / R O F Z RO F A / R O F Z RO F A / R O F Z RO F A / R O F Z RO F A / R O F Z RO F A / R O F Z RO F A / R O F Z RO F A / R O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z P O F Z R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A ROF A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A ROF A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A R O F A RS A RS A RS A RS A RS A RS A RS A RS A RS A RS A RS A RS A RS A RS A TS A NA T I O N A L G U A R D A V E APPROXIMATE ZONING BOUNDARY AIRPORT ZONING DISTRICT AIRPORT INDUSTRIAL ZONING DISTRICT WI L L I S T O N R O A D A I R P O R T D R I V E KENN E D Y D R I V E PROPOSED AVIATION TECH CENTER LOCATION BETA LEASE BOUNDARYEXISTING UTILITY EASEMENT 1 1 MIXED INDUSTRIAL & COMMERCIAL ZONING 1 CL I E N T : PR O J E C T : DRAWN DESIGNED CHECKED SCALE DATE PROJECT NO.DATE DESCRIPTION DRAWING TITLE DRAWING NUMBER PROJECT MILESTONE K: \ B U R L I N G T O N I N T E R N A T I O N A L A I R P O R T \ T - 1 8 7 1 5 . 0 2 A V I A T I O N T E C H N I C A L D E S I G N \ D R A W \ D R A W I N G S \ S H E E T F I L E S \ 1 8 7 1 5 . 0 2 - S I T E L O C A T I O N . D W G NOT FOR CONSTRUCTION 426 INDUSTRIAL AVENUE, SUITE 146 WILLISTON, VT 05495 P: (802)862-9381 WWW.MJINC.COM 81 Maple Street▪ Burlington VT 05401 802▪864▪6844▪ www.fffinc.com Architecture▪ Planning▪ Interiors BU R L I N G T O N A V I A T I O N T E C H N I C A L C E N T E R 20 0 D A V I N C I D R I V E , S O U T H B U R L I N G T O N , V T 0 5 4 0 3 BU R L I N G T O N S C H O O L D I S T R I C T BU R L I N G T O N , V E R M O N T OVERALL SKETCH PLAN 1"=80' ---- AJF AJF 18715.02 03/01/2024 SL-01 PERMIT SET SCALE 0 450 900 1350 FT LEGEND: LONG TERM EASEMENTS AND RIGHT OF WAYS AIRPORT PARCEL PROPOSED WORK AREA ZONING LINE BETA PUD BOUNDARY BETA LEASE BOUNDARY 1 4/10/2024 CITY COMMENTS S S D D D D FDFDFDFDFD FD FD FD FD FD FD FD FD FD FD FDFDFD D D D FD FD FD FD FDFD FD FDFDFD 8" ø G T S 8" ø G T R 4"PO P L A R ( 2 ) VEN T P I P E 14"M A P L E CO N C . W A L K FM FM FM SD SD SD FM FM FM F M F M F M F M F M FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM GATE 10"A P P L E EXISTING RETENTION BASIN EXISTING HANGER BUILDING EXISTING HANGER BUILDING EXISTING HANGER BUILDING PROPOSED BSD AVIATION TECHNICAL CENTER (REHABILITATION OF EXISTING HANGER BUILDING) EXISTING VERMONT FLIGHT ACADEMY BUILDING BETA TECHNOLOGIES BUILDING MILLINGS GRAVEL AREA ASPHALT PARKING AREA ASPHALT P A V E M E N T L I M I T EXISTING CONCRETE PAD EXISTING ASPHALT 44 ' 12 4 ' 23' 23 . 5 ' 25' EXISTING DUMPSTER ENCLOSURE FENCE EXISTING ASPHALT EXISTING HYDRANT EXISTING GATE CARD READER RETAINING WALL WITH HANDRAIL PUMP STATION PANEL EXISTING SANITARY PUMP STATION EXISTING ELECTRIC TRANSFORMER EXISTING 8-10" DIA. TREE (TYP.OF 4) VERMONT FLIGHT ACADEMY LEASE LINE BETA TECHNOLOGIES LEASE LINE ZONING BOUNDARY EXISTING SITE LIGHT TYP. EXISTING SECURITY GATE ASPHALT PAVEMENT LIMITS 1 NEW PLAN SHEET TO PROVIDE SEPARATE EXISTING CONDITIONS PLAN CL I E N T : PR O J E C T : DRAWN DESIGNED CHECKED SCALE DATE PROJECT NO.DATE DESCRIPTION DRAWING TITLE DRAWING NUMBER PROJECT MILESTONE K: \ B U R L I N G T O N I N T E R N A T I O N A L A I R P O R T \ T - 1 8 7 1 5 . 0 2 A V I A T I O N T E C H N I C A L D E S I G N \ D R A W \ D R A W I N G S \ E X - 0 1 A \ 1 8 7 1 5 . 0 2 _ E X - 0 1 A . D W G NOT FOR CONSTRUCTION 426 INDUSTRIAL AVENUE, SUITE 146 WILLISTON, VT 05495 P: (802)862-9381 WWW.MJINC.COM 81 Maple Street▪ Burlington VT 05401 802▪864▪6844▪ www.fffinc.com Architecture▪ Planning▪ Interiors BU R L I N G T O N A V I A T I O N T E C H N I C A L C E N T E R 20 0 D A V I N C I D R I V E , S O U T H B U R L I N G T O N , V T 0 5 4 0 3 BU R L I N G T O N S C H O O L D I S T R I C T BU R L I N G T O N , V E R M O N T SCALE 0 20 40 60 FT LEGEND: EXISTING BUILDINGS EXISTING GRAVEL AREA EXISTING SECURITY FENCE EXISTING UTILITY POLES EXISTING DRAINAGE STRUCTURES EXISTING STORM DRAINAGE STRUCTURES EXISTING PARKING LOT LIGHT FIXTURES EXISTING SEWER STRUCTURES EXISTING OVERHEAD ELECTRICAL WIRES EXISTING LEASE LINES D S EXISTING CONDITIONS PLAN 1"=20' DEL AJF AJF 18715.02 03/01/2024 EX-01A PERMIT SET 1 5/28/2024 CITY COMMENTS UE UE UE UE UE UE UE 20 ' 5' 5' WIDE CONCRETE WALK PROPOSED 35.55'X10' ENTRANCE CANOPY EXISTING DUMPSTER/COMPOST RECYCLING ENCLOSURE LEVEL 2 EV CHARGING STATION (2 PORTS) PROPOSED BOLLARD (TYP.OF 4) 8' HIGH CHAINLINK FENCE WITH VINYL SLAT WITH 16' WIDE MANUEL SWING GATE EXISTING ASPHALT PAVEMENT SLOPE TO BE MODIFIED PROPOSED FRONT CONCRETE ENTRANCE AREA (471 SF) BIKE RACKS - 8 PROPOSED COVERED BIKE SPACES EXISTING LOADING DOCK WALL WITH HANDRAIL TO REMAIN PROPOSED LAWN AREA NO PARKING SIGN SIDEWALK CURB RAMP (TYP.) 6" CONCRETE CURB 10' PROPOSED EMERGENCY GENERATOR PAD (16' X 5') PROPOSED TRANSFORMER VAULT PAD (SEE ELECTRICAL PLANS) (12.5' X 7') 5' 5' BETA INSTALLED SITE LIGHT DETECTABLE WARNING STRIPS (TYP) SIDEWALK RAMP (TYP) ADA PARKING SIGN ADA PARKING SIGN BETA INSTALLED SITE LIGHT PROPOSED BOLLARD DETECTABLE WARNING UNITS (TYP) DETECTABLE WARNING UNITS (TYP) PROPOSED OVERHEAD DOOR OVERHEAD DOORWAY BOLLARDS (TYP. OF 6) EXISTING OVERHEAD DOOR PROPOSED BSD AVIATION TECHNICAL CENTER (REHABILITATION OF EXISTING HANGER BUILDING) 27 . 7 1 ' GAS METER PROPOSED WHEEL STOPS BEGIN FLUSH CURB PROPOSED LANDSCAPING AREA (SEE DRAWING LL-01) MAIN ENTRANCE 2' 1' PROPOSED 6" CONCRETE CURB CL I E N T : PR O J E C T : K: \ B U R L I N G T O N I N T E R N A T I O N A L A I R P O R T \ T - 1 8 7 1 5 . 0 2 A V I A T I O N T E C H N I C A L D E S I G N \ D R A W \ D R A W I N G S \ S H E E T F I L E S \ 1 8 7 1 5 . 0 2 - L A Y O . D W G NOT FOR CONSTRUCTION 426 INDUSTRIAL AVENUE, SUITE 146 WILLISTON, VT 05495 P: (802)862-9381 WWW.MJINC.COM 81 Maple Street▪ Burlington VT 05401 802▪864▪6844▪ www.fffinc.com Architecture▪ Planning▪ Interiors BU R L I N G T O N A V I A T I O N T E C H N I C A L C E N T E R 20 0 D A V I N C I D R I V E , S O U T H B U R L I N G T O N , V T 0 5 4 0 3 BU R L I N G T O N S C H O O L D I S T R I C T BU R L I N G T O N , V E R M O N T SCALE 0 5 10 15 FT BLDG PLAN 1"=5' DEL AJF AJF 18715.02 03/01/2024 SP-02 PERMIT SET LEGEND PROPOSED HYDRANT LEASE LINES PROPOSED PAVEMENT REHABILITATION PROPOSED FULL DEPTH PAVEMENT PROPOSED LAWN AREA'S PROPOSED PEDESTRIAN WALKWAY MANDOOR OVERHEAD DOOR BOLLARD S S D D D D FDFDFDFDFD FD FD FD FD FD FD FD FD FD FD FDFDFD D D D FD FD FD FD FDFD FD FDFDFD 8" ø G T S 8" ø G T R 4"PO P L A R ( 2 ) VEN T P I P E 14"M A P L E CO N C . W A L K SD SD SD GATE 10"A P P L E EXISTING RETENTION BASIN EXISTING HANGER BUILDING EXISTING HANGER BUILDING EXISTING HANGER BUILDING PROPOSED BSD AVIATION TECHNICAL CENTER (REHABILITATION OF EXISTING HANGER BUILDING) EXISTING VERMONT FLIGHT ACADEMY BUILDING BETA TECHNOLOGIES BUILDING ADJUST RIM TO ±313.5 BETA SAND FILTER SYSTEM FFE=318' PROPOSED BIO RETENTION AREA EXISTING DMH98: 48" Ø RIM ELEV = 316.50' EXISTING DMH109: 48" Ø RIM ELEV = 319.05' EXISTING CB43: 60" Ø RIM ELEV = 316.50 TC=317.90' BC=317.90' CURRENT DRIVEWAY RECENTLY INSTALLED BY BETA TO REMAIN W W G G G UE EXISTING SD-142 RIM: 315.89 INV IN: 303.48 (15") INV IN: 304.20 (15") INV OUT: 306.02 (15") PROPOSED D-1 RIM: 312.55 INV OUT: 307.38 (15") EXISTING CB-63 RIM: 310.60 INV IN: 304.20 (15") INV OUT: 304.20 (15") EXISTING CB-66 RIM: 310.19 INV OUT: 304.58 (15") 312 3 1 3 315 31 2 3 1 2 312 31 3 314 316 317 318 317 TC=317.90 BC=317.40 TC=317.90 BC=317.40 317.33 317.09 317.10 317.40 317.54 320.49 319.00 317.84 314.50 313.00 312.90 313.76 313.15 312.57 311.67 314.00 316.00 315.50 TC=317.40 BC=317.40 MATCH EXISTING MATCH EXISTING MATCH EXISTING ASPHALT CONCRETE PAD ELEV. 318.00 GENERATOR PAD ELEV. 318.00 TRANSFORMER PAD ELEV. 318.00 318.00 MATCH EXISTING 317.00 MATCH EXISTING 12" THICK RIP RAP LINING TC=317.70 BC=317.90 BEGIN RETAINING WALL END RETAINING WALL (43.5 LF) 79.4 8 ' MIN. DISTANCE TO EXISTING WETLAND TOP OF BANK 1 CL I E N T : PR O J E C T : DRAWN DESIGNED CHECKED SCALE DATE PROJECT NO.DATE DESCRIPTION DRAWING TITLE DRAWING NUMBER PROJECT MILESTONE K: \ B U R L I N G T O N I N T E R N A T I O N A L A I R P O R T \ T - 1 8 7 1 5 . 0 2 A V I A T I O N T E C H N I C A L D E S I G N \ D R A W \ D R A W I N G S \ S H E E T F I L E S \ 1 8 7 1 5 . 0 2 - G R A D . D W G NOT FOR CONSTRUCTION 426 INDUSTRIAL AVENUE, SUITE 146 WILLISTON, VT 05495 P: (802)862-9381 WWW.MJINC.COM 81 Maple Street▪ Burlington VT 05401 802▪864▪6844▪ www.fffinc.com Architecture▪ Planning▪ Interiors BU R L I N G T O N A V I A T I O N T E C H N I C A L C E N T E R 20 0 D A V I N C I D R I V E , S O U T H B U R L I N G T O N , V T 0 5 4 0 3 BU R L I N G T O N S C H O O L D I S T R I C T BU R L I N G T O N , V E R M O N T SCALE 0 20 40 60 FT LEGEND EXISTING CONTOUR PROPOSED CONTOUR GRADING LIMITS EXISTING CATCH BASIN EXISTING DRAINAGE MANHOLE EXISTING DRAINAGE PIPE PAVEMENT RESURFACING AREA PROPOSED DRAINAGE PIPE SPOT ELEVATIONS (EXISTING/PROPOSED) 799 D GRADING & DRAINAGE 1"=20' JES AJF AJF 18715.02 03/01/2024 GR-01 PERMIT SET 1 4/10/2024 CITY COMMENTS 315.4/ S S D D D D FDFDFDFDFD FD FD FD FD FD FD FD FD FD FD FDFDFD D D D FD FD FD FD FDFD FD FDFDFD 8" ø G T S 8" ø G T R 4"PO P L A R ( 2 ) VEN T P I P E 10"A P P L E 14"M A P L E CO N C . W A L K FM FM FM FM FM FM F M F M F M F M F M FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM GATE W W G G G UE EXISTING BETA SITE LIGHT POLE, TYP. EXISTING UTILITY POLE TO REMAIN EXISTING UTILITY POLE TO REMAIN EXISTING STORM CATCH BASIN TO REMAIN EXISTING STORM CATCH BASIN TO REMAIN EXISTING BIO RETENTION BASIN EXISTING STORM CATCH BASIN TO REMAIN RELOCATE FIRE HYDRANT CAP EXISTING HYDRANT LATERAL EXISTING SANITARY PUMP STATION TO REMAIN & BE REFURBISHED EXISTING TRANSFORMER TO BE REMOVED EXISTING WATER SERVICE TO REMAIN (8" DI PIPE) SANITARY FORCEMAIN TO REMAIN (2" SCH 80 PVC) EXISTING HANGER BUILDING EXISTING HANGER BUILDING EXISTING HANGER BUILDING PROPOSED BSD AVIATION TECHNICAL CENTER (REHABILITATION OF EXISTING HANGER BUILDING) EXISTING VERMONT FLIGHT ACADEMY BUILDING BETA TECHNOLOGIES BUILDING EXISTING SANITARY FORCE MAIN BELIEVED TO BE ABANDONED 24' X 5' HVAC PAD AREA NEW PUMP STATION CONTROL PANEL PROPOSED DRAINAGE INLET & PIPE 12.5' PROPOSED EMERGENCY GENERATOR (SEE ELECTRICAL PLANS) EXISTING WATER SERVICE TO REMAIN (SEE PLUMBING PLANS) PROPOSED TRANSFORMER (SEE ELECTRICAL PLANS) RELOCATED 2" GAS SERVICE (SEE BUILDING PLANS) RELOCATED FIRE HYDRANT NEW TAPPING SLEEVE & VALVE ON EXISTING 8" DI WATER LINE UNDERGROUND ELECTRICAL SERVICE TO EV CHARGING STATION (SEE ELECTRICAL PLANS) WINTER SERVICE ROOM ELECTRICAL SERVICE ROOM CL I E N T : PR O J E C T : DRAWN DESIGNED CHECKED SCALE DATE PROJECT NO.DATE DESCRIPTION DRAWING TITLE DRAWING NUMBER PROJECT MILESTONE K: \ B U R L I N G T O N I N T E R N A T I O N A L A I R P O R T \ T - 1 8 7 1 5 . 0 2 A V I A T I O N T E C H N I C A L D E S I G N \ D R A W \ D R A W I N G S \ S H E E T F I L E S \ 1 8 7 1 5 . 0 2 - U T I L . D W G NOT FOR CONSTRUCTION 426 INDUSTRIAL AVENUE, SUITE 146 WILLISTON, VT 05495 P: (802)862-9381 WWW.MJINC.COM 81 Maple Street▪ Burlington VT 05401 802▪864▪6844▪ www.fffinc.com Architecture▪ Planning▪ Interiors BU R L I N G T O N A V I A T I O N T E C H N I C A L C E N T E R 20 0 D A V I N C I D R I V E , S O U T H B U R L I N G T O N , V T 0 5 4 0 3 BU R L I N G T O N S C H O O L D I S T R I C T BU R L I N G T O N , V E R M O N T SCALE 0 20 40 60 FT LEGEND EXISTING CATCH BASIN EXISTING DRAINAGE MANHOLE EXISTING DRAINAGE PIPE EXISTING/PROPOSED HYDRANT FORCE MAIN WATER OVERHEAD ELECTRICAL WIRES UNDERGROUND ELECTRICAL WIRES EXISTING LIGHT POLES D FM UE UTILITY PLANS 1"=20' DEL AJF AJF 18715.02 03/01/2024 UT-01 PERMIT SET S S D D D D FDFDFDFDFD FD FD FD FD FD FD FD FD FD FD FDFDFD D D D FD FD FD FD FDFD FD FDFDFD 8" ø G T S 8" ø G T R 4"PO P L A R ( 2 ) VEN T P I P E 10"A P P L E 14"M A P L E CO N C . W A L K FM FM FM SD SD SD FM FM FM F M F M F M F M F M FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM GATE W W G G G UE EXISTING RETENTION BASIN EXISTING HANGER BUILDING EXISTING HANGER BUILDING EXISTING HANGER BUILDING PROPOSED BSD AVIATION TECHNICAL CENTER (REHABILITATION OF EXISTING HANGER BUILDING) EXISTING VERMONT FLIGHT ACADEMY BUILDING BETA TECHNOLOGIES BUILDING ADJUST RIM TO ±313.5 RIM INV. BETA SAND FILTER SYSTEM FFE=318' CONCRETE WASHOUT AREA 312.00 EXISTING SD-142 RIM: 315.89 INV IN: 303.48 (15") INV IN: 304.20 (15") INV OUT: 306.02 (15") PROPOSED D-1 RIM: 312.55 INV OUT: 307.38 (15") EXISTING CB-63 RIM: 310.60 INV IN: 304.20 (15") INV OUT: 304.20 (15") EXISTING CB-66 RIM: 310.19 INV OUT: 304.58 (15") 314.69 315.04 315.40 314.50 313.62 316.00314.00 313.00 312.50 312.00 313.00311.67 313.75 313.15 312.72 SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF SF IP IP IP 316 317 318 319 315 31 2 31 3 314 3 1 2 3 1 3 317 3 1 2 IP SF SF SF PROPOSED SILT FENCE SITE DEMARCATION FENCE SITE DEMARCATION FENCE SITE DEMARCATION FENCE CL I E N T : PR O J E C T : DRAWN DESIGNED CHECKED SCALE DATE PROJECT NO.DATE DESCRIPTION DRAWING TITLE DRAWING NUMBER PROJECT MILESTONE K: \ B U R L I N G T O N I N T E R N A T I O N A L A I R P O R T \ T - 1 8 7 1 5 . 0 2 A V I A T I O N T E C H N I C A L D E S I G N \ D R A W \ D R A W I N G S \ S H E E T F I L E S \ 1 8 7 1 5 . 0 2 - E R O S . D W G NOT FOR CONSTRUCTION 426 INDUSTRIAL AVENUE, SUITE 146 WILLISTON, VT 05495 P: (802)862-9381 WWW.MJINC.COM 81 Maple Street▪ Burlington VT 05401 802▪864▪6844▪ www.fffinc.com Architecture▪ Planning▪ Interiors BU R L I N G T O N A V I A T I O N T E C H N I C A L C E N T E R 20 0 D A V I N C I D R I V E , S O U T H B U R L I N G T O N , V T 0 5 4 0 3 BU R L I N G T O N S C H O O L D I S T R I C T BU R L I N G T O N , V E R M O N T SCALE 0 20 40 60 FT LEGEND EXISTING CONTOUR PROPOSED CONTOUR GRADING LIMITS EXISTING CATCH BASIN EXISTING DRAINAGE MANHOLE EXISTING DRAINAGE PIPE INLET PROTECTION 799 D IP EROSION PREVENTION & SEDIMENTATION CONTROL 1"=20' JES AJF AJF 18715.02 03/01/2024 EPSC-01 PERMIT SET S S D D FD FDFDFDFDFD FD FD FD FD FD FD FD FD FD FD FDFDFDFD D D D FD FD FD FD FDFD FD FDFDFD 8" ø G T S 8" ø G T R FM FM FM FM FM FM FM FM FM FM FM FM FMEXISTING HANGER BUILDING PROPOSED BSD AVIATION TECHNICAL CENTER (REHABILITATION OF EXISTING HANGER BUILDING) BETA TECHNOLOGIES BUILDING EXISTING BETA SITE LIGHT POLE, TYP. EXISTING TREE TYP. 5.3 4.2 2.8 5.8 5.6 4.4 3.0 1.9 4.4 5.0 4.7 3.8 2.6 1.7 1.1 3.3 3.6 3.7 3.5 2.9 2.1 1.4 3.8 3.2 2.9 2.7 2.4 2.0 1.5 5.5 4.2 3.1 2.4 2.0 1.7 1.4 6.6 6.4 5.4 4.0 2.9 2.1 1.6 1.3 5.7 5.5 5.3 4.5 3.4 2.4 1.7 4.0 3.7 3.2 2.5 1.8 2.4 2.1 1.71.4 3.72.8 4.7 3.9 1.6 2.7 7.6 12.8 5.8 0.8 0.7 1.7 4.5 8.8 10.0 1.6 0.5 0.4 0.4 0.4 0.8 1.9 4.7 4.9 1.7 0.8 0.2 0.2 0.2 0.2 0.3 0.4 0.8 1.5 1.7 1.2 0.9 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.5 0.7 0.9 1.0 1.5 2.3 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.5 0.7 1.2 2.8 8.0 11.6 0.1 0.1 0.1 0.2 0.2 0.3 0.4 0.7 1.2 3.0 9.9 18.3 15.7 0.1 0.1 0.1 0.2 0.3 0.4 0.6 1.1 2.3 5.3 13.7 15.6 10.6 0.1 0.1 0.2 0.2 0.4 0.6 1.0 1.7 3.4 6.5 8.7 8.2 6.0 0.1 0.1 0.2 0.3 0.5 0.8 1.3 2.2 3.5 4.7 4.8 3.8 2.5 0.1 0.1 0.2 0.2 0.4 0.6 0.9 1.4 2.0 2.5 2.6 2.2 1.7 1.4 0.1 0.1 0.2 0.3 0.4 0.6 0.9 1.2 1.4 1.5 1.4 1.3 1.3 0.1 0.2 0.2 0.3 0.4 0.6 0.7 0.9 0.9 1.0 1.2 1.5 2.2 0.1 0.2 0.2 0.3 0.4 0.5 0.6 0.7 0.9 1.2 1.9 3.1 5.1 0.1 0.2 0.2 0.3 0.3 0.4 0.6 0.8 1.3 2.1 3.9 6.8 9.9 0.1 0.2 0.2 0.3 0.4 0.5 0.7 1.2 2.1 3.9 6.8 9.9 10.3 0.1 0.2 0.2 0.3 0.4 0.7 1.1 1.8 3.1 5.1 7.0 7.3 6.1 0.1 0.2 0.2 0.3 0.5 0.8 1.4 2.1 3.2 4.1 4.3 0.1 0.2 0.3 0.4 0.6 0.9 1.4 1.8 2.3 0.1 0.2 0.2 0.3 0.4 0.6 0.9 1.1 0.1 0.2 0.2 0.3 0.4 0.1 0.2 0.20.1 0.30.8 0.5 0.4 0.7 2.0 1.6 1.2 0.9 0.6 1.3 1.1 1.0 0.8 2.9 2.7 2.2 1.8 1.4 1.0 0.7 1.8 1.8 1.7 1.5 1.2 0.9 2.4 3.0 3.7 3.4 3.0 2.5 2.0 1.5 1.0 0.7 2.4 2.5 2.6 2.5 2.3 1.9 1.3 2.6 3.3 3.6 4.2 4.2 3.6 3.2 2.6 2.0 1.5 1.1 2.8 3.1 3.3 3.7 3.8 3.6 2.9 1.8 1.1 3.7 4.9 4.1 3.9 3.8 3.6 3.2 2.7 2.1 1.6 1.4 3.1 3.6 4.0 4.2 5.0 5.7 5.6 3.9 2.4 1.4 0.8 0.6 4.3 4.5 3.9 3.8 3.8 3.6 3.2 2.7 2.2 1.9 1.9 3.4 4.1 4.7 4.9 5.2 6.3 8.0 7.2 4.9 2.9 1.7 1.0 3.7 4.5 4.3 4.5 4.1 4.0 3.7 3.2 2.8 2.6 2.8 3.9 4.4 5.0 5.6 5.6 6.7 7.8 8.8 7.8 5.7 3.5 3.6 5.2 4.8 4.2 4.3 4.3 3.9 3.5 3.5 3.7 4.0 4.4 4.8 5.2 5.5 5.7 7.0 7.3 8.2 8.1 7.5 5.6 3.6 4.5 4.5 4.5 4.9 4.5 4.3 4.4 4.6 4.9 5.2 5.8 6.1 6.2 6.6 6.8 3.6 6.8 6.3 5.7 3.9 4.9 4.9 4.8 4.8 4.8 5.0 5.4 5.6 6.1 7.4 8.3 8.3 7.3 6.6 5.6 3.3 4.3 5.1 4.6 4.4 4.9 5.5 6.0 6.2 7.1 9.3 11.5 11.2 8.0 5.5 4.1 4.4 4.4 4.5 5.2 5.9 6.5 6.8 8.9 14.2 15.0 11.1 7.6 5.2 4.1 5.0 5.4 5.9 6.2 8.4 14.7 22.0 15.8 8.7 4.7 5.0 4.8 5.9 8.5 15.7 19.0 7.8 4.0 4.2 4.9 5.9 6.2 5.0 3.6 3.8 3.3 3.0 FL1 FL1 FL1 FL1 WP1 WP1 FL1 FL1WP1 CL I E N T : PR O J E C T : DRAWN DESIGNED CHECKED SCALE DATE PROJECT NO.DATE DESCRIPTION DRAWING TITLE DRAWING NUMBER PROJECT MILESTONE K: \ B U R L I N G T O N I N T E R N A T I O N A L A I R P O R T \ T - 1 8 7 1 5 . 0 2 A V I A T I O N T E C H N I C A L D E S I G N \ D R A W \ D R A W I N G S \ S H E E T F I L E S \ 1 8 7 1 5 . 0 2 - L I G H T I N G - E . D W G NOT FOR CONSTRUCTION 426 INDUSTRIAL AVENUE, SUITE 146 WILLISTON, VT 05495 P: (802)862-9381 WWW.MJINC.COM 81 Maple Street▪ Burlington VT 05401 802▪864▪6844▪ www.fffinc.com Architecture▪ Planning▪ Interiors BU R L I N G T O N A V I A T I O N T E C H N I C A L C E N T E R 20 0 D A V I N C I D R I V E , S O U T H B U R L I N G T O N , V T 0 5 4 0 3 BU R L I N G T O N S C H O O L D I S T R I C T BU R L I N G T O N , V E R M O N T SCALE 0 20 40 60 FT LEGEND EXISTING SITE LIGHT POLES EXISTING BUILDING MOUNTED LIGHTS EXISTING TREES EXISTING LIGHTING & LANDSCAPING ---- ---- AJF AJF 18715.02 03/01/2024 LL-01 PERMIT SET FL1/WP1 Luminaire Schedule Symbol Qty Label Arrangement Total Lamp Lumens LLF Description Lum. Watts 4 Exist Pole SINGLE N.A.0.950 GALN-SA6A-740-U-T4W 182 6 EX FL1 SINGLE 8522640 1.000 EXISTING FLOOD LIGHT 75 3 EX WP1 SINGLE N.A.1.000 EXISTING WALL PACK 40