Loading...
HomeMy WebLinkAboutSD-23-05 - Supplemental - 0760 Shelburne Road (57)SOUTH BURLINGTON WATER DEPARTMENT 403 Queen City Park Road South Burlington, VT 05403 Phone: (802) 864-4361 Fax: (802) 864-0435 www.sburl.com SBWD Technical Review Comments SP-23-05 760 Shelburne Rd. Date: July 2, 2023 Submitted by: Jay Nadeau, SBWD Superintendent It is the responsibility of the contractor to be familiar with the CWD Specifications beyond what is included in this information. The Champlain Water District Specifications and Detail for the Installation of Water Lines and Appurtenances information can be found at www.champlainwater.org Plan Specific Comments Sheet C3-01. (See sheet C3-01) 1. The proposed eight-inch (8”) tee shall include a main line gate valve on either side of the new tee to be cut-in, secured to the tee with Foster Adapters; total three (3) eight-inch gate valves. This must be shown on the plans. The cut-in of this tee shall require a shutdown on the only line supplying the northern part of the City so must be scheduled for night work. At least three weeks’ notice must be provided to the SBWD so all affected customers can be notified in advance of the water service interruption. 2. Include a tracing wire box near tee per CWD Specifications. 3. A six-inch (6”) valve on the line supplying the Multi-family Residential 27DU building shall be secured to the hydrant tee. Add a tracing wire box to this tee, per CWD Specifications. 4. Place the 1.5” curb box inside a gate valve box top when located in concrete or asphalt surface areas. Include a minimum 1” paving riser. 5. Locate and abandon all three existing water services at the corporations. Close the corporations, disconnect the service lines, and wrap the service taps in V-Bio polyurethane. 6. The services to all of the proposed buildings shall be copper and DI if petroleum infused soils are encountered. See VT Water Supply Rule requirements. 7. Install 6” gate valve on FS line to 27 DU Multifamily Residential building. Add tracing wire box per CWD Specifications. 8. See CWD Specifications for tracing wire requirements for all PVC water pipe. 9. Sheet C8-04 1. Water Details must be those found in the CWD Specifications. The Department will not accept any pipe or material that is not in compliance with the CWD Specifications. There are too many discrepancies to list here between Sheet C8-04 Water Details and the CWD Specifications.