HomeMy WebLinkAboutSP-22-060 - Supplemental - 0339 Garden Street (42)SOUTH BURLINGTON WATER DEPARTMENT
403 Queen City Park Road
South Burlington, VT 05403
Phone: (802) 864-4361
Fax: (802) 864-0435
www.sburl.com
SBWD Technical Review Comments SP-22-060, Market St Lot B.
Date: December 15, 2022
Submitted by Jay Nadeau, SBWD Director
RESPONSES ADDED 12-16-22 BY ANDREW ROWE
I have provided the following comments in greater detail directly on the Civil Plans for this project.
1. Record Drawings prepared by a VT licensed Professional Engineer shall be provided to the South
Burlington Water Department in pdf. and Auto-CAD format. Drawings shall include ties to all gate
valves and curb stops to sub-meter accuracy.
UNDERSTOOD
Sheet 4
2. Hydrant on island must be set away from any planting to provide access.
THE HYDRANT HAS BEEN MOVED TO THE MIDDLE OF THE ISLAND TO ACHIEVE
SEPARATION FROM PLANTINGS – SEE SHEET 4
3. Fire hydrant on island will be considered private and subject to all requirements stated within the South
Burlington Water Ordinance.
UNDERSTOOD
4. Tree on Garden Street side near access road must be relocated or removed altogether to provide access
to fire hydrant.
TREE TO BE RELOCATED TO OPPOSITE SIDE OF SIDEWALK RAMP – SEE SHEET 4
5. Tap for Building B1:
a. Remove stub from existing 8” gate valve. Install cap with Foster Adapters to gate valve. Install
pre-cast thrust block.
DONE – SEE SHEET 4
6. Tap existing 12” water main for new 6” service to Buidling B1. Install a separate 2” tap for domestic
service at least 5’ away from FS tap on water main.
DONE – SEPARATE 6” AND 2” SERVICES SHOWN WITH NEW CONNECTIONS. SEE SHEETS
4 & 10
7. Proposed 6” FS line to Building 1 jeopardizes the integrity of the 12” water main. Remove this design.
DONE – SEE SHEET 4
Sheet 9
8. Can foundation wall be penetrated for FS and domestic water services to avoid going under and up
through the slabs?
DETAIL REVISED TO SHOW SERVICES ENTERING THROUGH FOUNDATION WALL – SEE
SHEETS 4 & 10. THIS IS THE PREFERENCE FOR INSTALLATION.
Sheet 10
9. Detail-Building B3:If gas line will not be used, can it be removed at the gas main?
SOUTH BURLINGTON WATER DEPARTMENT
403 Queen City Park Road
South Burlington, VT 05403
Phone: (802) 864-4361
Fax: (802) 864-0435
www.sburl.com
THIS GAS SLEEVE IS NOT NEEDED TO SERVE EITHER OF THE NEW BUILDINGS. THE GAS
SLEEVE WILL BE CUT BACK TO BEHIND THE CURB. SEE SHEET 10.
10. Detail-Building B3: tap for water line must be no less than 5’ away from existing gas main.
THE GAS SLEEVE WILL BE CUT BACK AND IS NOT NEEDED FOR EITHER OF THE NEW
BUILDINGS. NO GAS SERVICE NEEDED IN THIS AREA.
11. Detail-Building B1: See comments on Sheet 4.
SHEET 4 REVISED
12. Detail Building B2: Since a domestic tap is proposed on the FS line, then a second FS gate valve must
be installed downstream of the domestic water service tap.
A SECOND 6” GATE VALVE HAS BEEN ADDED TO ALLOW THE FS LINE TO BE ISOLATED
– SEE SHEETS 4 & 10