Loading...
HomeMy WebLinkAboutSP-22-060 - Supplemental - 0224 0268 Market Street (45)SOUTH BURLINGTON WATER DEPARTMENT 403 Queen City Park Road South Burlington, VT 05403 Phone: (802) 864-4361 Fax: (802) 864-0435 www.sburl.com SBWD Technical Review Comments SP-22-060, Market St Lot B. Date: December 15, 2022 Submitted by Jay Nadeau, SBWD Director RESPONSES ADDED 12-16-22 BY ANDREW ROWE I have provided the following comments in greater detail directly on the Civil Plans for this project. 1. Record Drawings prepared by a VT licensed Professional Engineer shall be provided to the South Burlington Water Department in pdf. and Auto-CAD format. Drawings shall include ties to all gate valves and curb stops to sub-meter accuracy. UNDERSTOOD Sheet 4 2. Hydrant on island must be set away from any planting to provide access. THE HYDRANT HAS BEEN MOVED TO THE MIDDLE OF THE ISLAND TO ACHIEVE SEPARATION FROM PLANTINGS – SEE SHEET 4 3. Fire hydrant on island will be considered private and subject to all requirements stated within the South Burlington Water Ordinance. UNDERSTOOD 4. Tree on Garden Street side near access road must be relocated or removed altogether to provide access to fire hydrant. TREE TO BE RELOCATED TO OPPOSITE SIDE OF SIDEWALK RAMP – SEE SHEET 4 5. Tap for Building B1: a. Remove stub from existing 8” gate valve. Install cap with Foster Adapters to gate valve. Install pre-cast thrust block. DONE – SEE SHEET 4 6. Tap existing 12” water main for new 6” service to Buidling B1. Install a separate 2” tap for domestic service at least 5’ away from FS tap on water main. DONE – SEPARATE 6” AND 2” SERVICES SHOWN WITH NEW CONNECTIONS. SEE SHEETS 4 & 10 7. Proposed 6” FS line to Building 1 jeopardizes the integrity of the 12” water main. Remove this design. DONE – SEE SHEET 4 Sheet 9 8. Can foundation wall be penetrated for FS and domestic water services to avoid going under and up through the slabs? DETAIL REVISED TO SHOW SERVICES ENTERING THROUGH FOUNDATION WALL – SEE SHEETS 4 & 10. THIS IS THE PREFERENCE FOR INSTALLATION. Sheet 10 9. Detail-Building B3:If gas line will not be used, can it be removed at the gas main? SOUTH BURLINGTON WATER DEPARTMENT 403 Queen City Park Road South Burlington, VT 05403 Phone: (802) 864-4361 Fax: (802) 864-0435 www.sburl.com THIS GAS SLEEVE IS NOT NEEDED TO SERVE EITHER OF THE NEW BUILDINGS. THE GAS SLEEVE WILL BE CUT BACK TO BEHIND THE CURB. SEE SHEET 10. 10. Detail-Building B3: tap for water line must be no less than 5’ away from existing gas main. THE GAS SLEEVE WILL BE CUT BACK AND IS NOT NEEDED FOR EITHER OF THE NEW BUILDINGS. NO GAS SERVICE NEEDED IN THIS AREA. 11. Detail-Building B1: See comments on Sheet 4. SHEET 4 REVISED 12. Detail Building B2: Since a domestic tap is proposed on the FS line, then a second FS gate valve must be installed downstream of the domestic water service tap. A SECOND 6” GATE VALVE HAS BEEN ADDED TO ALLOW THE FS LINE TO BE ISOLATED – SEE SHEETS 4 & 10