Loading...
HomeMy WebLinkAboutSP-22-032 - Supplemental - 0119 Tilley Drive (52)SOUTH BURLINGTON WATER DEPARTMENT 403 Queen City Park Road South Burlington, VT 05403 Phone: (802) 864-4361 Fax: (802) 864-0435 www.sburl.com SBWD Technical Review Comments 119 Tilley Drive Date: July 21, 2022 Submitted by Jay Nadeau, SBWD Director Site specific comments can be found on plan sheets. 1. Plans must include a note stating “All water lines and appurtenances shall be installed in accordance with the Champlain Water District Specifications and Details for the Installation of Water Lines and Appurtenances, current edition.” 2. Record Drawings prepared by a VT licensed Professional Engineer shall be provided to the South Burlington Water Department in pdf. and Auto-CAD format. Drawings shall include ties to all gate valves and curb stops to sub-meter accuracy. 3. Attach the domestic line gate valve to the fire sprinkler line tee and gate valve. Sheet C-1.5 4. Install two 45-degree bends on domestic water line prior to entering building. Sheet C-1.5 5. Install hydrant isolation valve on upstream side of 45-degree bend. Remove hydrant gate valve that is shown near hydrant. Sheet C-1.7 6. New fire hydrant to include 4” Storz connection and spring- loaded hydrant flag. 7. Fire hydrant shall be considered private since it will be on a fire sprinkler line dedicated to this facility.