HomeMy WebLinkAboutSD-22-07 - Plans - Non-Record - 0047 Cheesefactory RoadPIPE TRENCH DETAIL
NOT TO SCALE
MOUND 3" ABOVE GRADE TO
ALLOW FOR SETTLEMENT. FINISH
WITH TOPSOIL, SEED, AND MULCH
UNDISTURBED SOIL
SEE SITE PLAN FOR
PIPE SIZE AND TYPE
THROUGHLY COMPACTED
BEDDING MATERIAL
1.BEDDING MATERIAL FOR WASTEWATER LINES SHALL CONSIST OF CRUSHED STONE
WITH A MAXIMUM SIZE OF 34" (FOR WATER LINES, BEDDING SHALL BE SAND)
2.BEDDING MATERIAL SHALL NOT BE PLACED ON FROZEN GROUND.
3.TRENCH SHALL BE COMPLETELY DEWATERED PRIOR TO PLACING PIPE AND BEDDING
MATERIAL
4.MAINTAIN A MINIMUM OF 4'6" COVER ABOVE PIPE (5'6" ABOVE ALL WATER LINES OR
OTHER PIPES IN PLOWED AREAS). INSTALL 2" RIGID INSULATION IF COVER IS 3'6"-4'6",
AND USE 4" INSULATION IF COVER IS 2'6"-3'6". INSULATION TO BE 4' WIDE.
COMPACTED CLEAN
BACKFILL- NO STONES
GREATER THAN 6"
LEAKAGE AND PRESSURE TESTING NOTES
1.WASTEWATER PIPING
1.a.NEW GRAVITY AND FORCE MAIN PIPES SHALL BE PRESSURE TESTED DURING INSTALLATION
AND OBSERVED BY MMES OR THE CERTIFYING DESIGNER.
1.b.SANITARY SEWER COLLECTION PIPE TESTING SHALL COMPLY WITH VERMONT
ENVIRONMENTAL PROTECTION RULES (VT EPR) CHAPTER 1, SECTION 1-1003(o).
2.WATER PIPING
2.a.POTABLE WATER SUPPLY PIPING SHALL BE PRESSURE TESTED DURING INSTALLATION AND
OBSERVED BY MMES OR THE CERTIFYING DESIGNER.
2.b.WATER SUPPLY PIPE TESTING SHALL COMPLY WITH VT EPR CHAPTER 1, SECTION 1-1209.
D + 24"6" MINIMUM
D
6" MINIMUM
OFFSET SAW CUT IN ASPHALT
A MINIMUM OF 6" FROM
TRENCH EXCAVATION
MATCH EXISTING SUBBASE MATERIAL
AND THICKNESS OR INSTALL AS
DIRECTED BY ENGINEER
ROAD
MATCH EXISTING ASPHALT THICKNESS
LAWN
SEE NOTE 4
WARNING TAPE
CASING TO EXTEND MINIMUM
10' INTO COMPETENT BEDROCK
DRILLED BEDROCK WELL DETAIL
NOT TO SCALE
6" STEEL WELL CASING, INSTALL
MINIMUM 20'
COMPETENT BEDROCK
ELECTRICAL CONDUIT,
BURIED MINIMUM 18"
FINISHED GRADE TO SLOPE
AWAY FROM WELL CASING
ELECTRICAL WIRE
WATERTIGHT VENTED WELL
CAP
SUBMERSIBLE WELL PUMP
INSTALL MINIMUM 20'
FROM BOTTOM
DRIVE SHOE
NON-SHRINK GROUT
INSTALL PER SECTION 12.2.3
AND 12.3.14 OF THE WATER
SUPPLY RULES
WATER SERVICE LINE
SEE SITE PLAN FOR SIZING
RISER PIPE (SIZE AS REQUIRED)
TORQUE ARRESTOR
PITLESS ADAPTER
WELL CASING TO EXTEND
MINIMUM 18" ABOVE GRADE
LOW WATER LEVEL ALARM
CHECK VALVE
NOTE: THE FOLLOWING NOTES REFERENCE THE VERMONT ENVIRONMENTAL PROTECTION RULES
CHAPTER 1 WASTEWATER SYSTEM AND POTABLE WATER SUPPLY RULES, EFFECTIVE 4/12/2019 (THE RULES).
WATER SERVICE LINES AND PIPES SHALL BE PRESSURE AND LEAKAGE TESTED PER SECTION 1-1209 OF THE
RULES. WATER SYSTEMS SHALL BE DISINFECTED PER SECTION 1-1210 OF THE RULES. SEE TABLE 11-1 FOR
HORIZONTAL ISOLATION DISTANCES FROM POTENTIAL SOURCES OF CONTAMINATION TO A POTABLE
WATER SOURCE, AND WATER SERVICE PIPES/LINES.
LOT 2 PUMP STATION DESIGN
PUMP DESIGN:
-Install MYERS ME3F (0.33HP) Effluent Pump or Approved Equal
-Pump Head Available: 25.0' @ 25± GPM
-Friction Loss: 3.5'±
-Elevation Head Loss: 1'±
-Net Head at Leachfield: 20.5'±
DESIGN DOSE
-Design Dose (5 x distribution piping volume)
→ 5 x (V) → 5 x {(34" ÷ 12"/ft)2 ∏ x 140'} x 7.48 gal/ft3= 64 gallons
-Actual Dose Volume
→ 7.0" dose x 10± gal/inch = 70± gal/dose
-Doses per Day
→ 490 gpd ÷ 70 gal/dose = 7± doses per day
-Total Number of Orifices in Distribution Piping
→ 30
-Proposed Leachfield Area per Orifice must be less than 25sf/orifice
→ LA ÷ Orifice = 525s.f. ÷ 30 orifices = 17.5 sf/orifice
SEE ORIFICE FLOW CALCULATIONS FOR ADDITIONAL DETAIL
5"
4"
8"3"
56"
68"
53"
4" PVC PIPE
4" CAST IN SEAL (TYP. OF 3)
3" CARBON VENT
11
4" COUPLING
24"Ø RISER
CAST IN SEAL
FOR 1 12" PVC PIPE
1 1/2"Ø PVC PIPE
20"Ø RISER
16"Ø RISER
81.5"6"38"4.5"4.5"
26"
1500-GALLON STEP TANK
NOT TO SCALE49" FLUID LEVEL4" INLET
TEE BAFFLE
4" OUTLET TEE
BAFFLE WITH
STATE
APPROVED
FILTER
4" INVERT OUT: SEE SITE PLAN4"Ø SCH. 40 INVERT IN
SEE SITE PLAN FOR
INVERT ELEVATIONS
3" CARBON FILTER
RISER LID
WATER TIGHT
JUNCTION BOX
1 1/2" TRI-CHECK VALVE
(UNION/ CHECK VALVE / BALL
VALVE COMBINATION)
INSTALL MYERS ME3F SERIES (0.33
HP) PUMP OR APPROVED EQUAL
CAST IN SEAL FOR 1 1/2" PVC PIPE
1
4"Ø WEEP HOLE IN 90° FITTING
1 1/2"Ø SCH 80 PVC FITTINGS
11/2"Ø SDR 21 PVC FORCE MAIN
INSTALL FLOAT FOR 70 GAL. DOSE
LOT 3 PUMP STATION DESIGN
PUMP DESIGN:
-Install MYERS ME3F (0.33HP) Effluent Pump or Approved Equal
-Pump Head Available: 26' @ 23± GPM
-Friction Loss: 3.1'±
-Elevation Head Loss: -2'±
-Net Head at Leachfield: 24.9'±
DESIGN DOSE
-Design Dose (5 x distribution piping volume)
→ 5 x (V) → 5 x {(34" ÷ 12"/ft)2 ∏ x 120'} x 7.48 gal/ft3= 55 gallons
-Actual Dose Volume
→ 7.0" dose x 10± gal/inch = 70± gal/dose
-Doses per Day (4 minimum required)
→ 490 gpd ÷ 70 gal/dose = 7± doses per day
-Total Number of Orifices in Distribution Piping
→ 25
-Proposed Leachfield Area per Orifice must be less than 25sf/orifice
→ LA ÷ Orifice = 490s.f. ÷ 25 orifices = 19.6 sf/orifice
SEE ORIFICE FLOW CALCULATIONS FOR ADDITIONAL DETAIL
LOT 4 PUMP STATION DESIGN
PUMP DESIGN:
-Install MYERS ME3F (0.33HP) Effluent Pump or Approved Equal
-Pump Head Available: 26' @ 21.5± GPM
-Friction Loss: 2.4'±
-Elevation Head Loss: 2'±
-Net Head at Leachfield: 21.6'±
DESIGN DOSE
-Design Dose (5 x distribution piping volume)
→ 5 x (V) → 5 x {(34" ÷ 12"/ft)2 ∏ x 120'} x 7.48 gal/ft3= 46 gallons
-Actual Dose Volume (4 minimum required)
→ 7.0" dose x 10± gal/inch = 70± gal/dose
-Doses per Day
→ 490 gpd ÷ 70 gal/dose = 7± doses per day
-Total Number of Orifices in Distribution Piping
→ 25
-Proposed Leachfield Area per Orifice must be less than 25sf/orifice
→ LA ÷ Orifice = 490s.f. ÷ 25 orifices = 19.6 sf/orifice
SEE ORIFICE FLOW CALCULATIONS FOR ADDITIONAL DETAIL
LOT 3 & 4 SINGLE TRENCH MOUND
CROSS-SECTION
NOT TO SCALE
LOT 3 & 4 WASTEWATER TRENCH
PLAN VIEW
NOT TO SCALE
12" SOIL COVER OVER ENTIRE MOUND.
TOP 3-4" TO BE TOPSOIL; PLACE SEED,
AND MULCH
EXTEND MOUND SAND 1'
HORIZONTALLY FROM STONE
CUT VEGETATION FLUSH TO GRADE. LEAVE ROOTS IN PLACE
(IF APPLICABLE). PLOW EXISTING GRADE TO A DEPTH OF 7-8".
DO NOT DRIVE CONSTRUCTION EQUIPMENT OVER THE
PLOWED SURFACE UNTIL A MINIMUM 6" LIFT IS INSTALLED.
1.5"∅ SDR 21 PVC PIPE
FROM PUMP STATION
1.5"∅ SCH 40 PVC 90° LONG
/SWEEP ELBOW
4'0"
3
1
INSTALL MIRAFI 140N FILTER FABRIC
OR APPROVED EQUAL OVER TOP OF
STONE LEACHFIELD
1.5"Ø SCH 40 PVC SOLVENT PRIMED AND
WELDED (SEE PRESSURE DISTRIBUTION
SYSTEM DETAILS BELOW)
BOTTOM OF STONE TRENCH
LOT 2 ELEVATION: 391.5±
LOT 3 ELEVATION: 395.5±
MIN. 20" SAND REQUIRED
BELOW STONE TRENCH
MIN. 6" STONE
BELOW PIPE
125'
4'
3
4 - 11
2" WASHED CRUSHED STONE
INSTALL TWENTY-FIVE (25) TOTAL 1/8"∅
ORIFICES WITH ORIFICE SHIELDS (TYP.)
FACING DOWNWARDS 1 1/2"∅ SDR 21 PVC FORCE MAIN
PIPE FROM PUMP STATION
INSTALL FLUSHING VALVE,
SEE DETAIL, THIS SHEET
5' (TYP.)2.5' (TYP.)INSTALL 1.5"Ø SCH. 40 PVC PIPE.
SOLVENT WELD JOINTS
MIN. 12" STONE
1'9"
LOT 2 BED IN MOUND CROSS-SECTION
NOT TO SCALE
LOT 2 WASTEWATER BED PLAN VIEW
NOT TO SCALE
75'
7'
5' (TYP.)
34 - 112" WASHED CRUSHED STONE
INSTALL FIFTEEN (15) 1/8"Ø ORIFICES PER
LATERAL (THIRTY TOTAL) WITH ORIFICE
SHIELDS FACING DOWNWARD (TYP.)1 1/2"∅ SDR 21 PVC FORCE MAIN
PIPE FROM PUMP STATION
37.5'
INSTALL FLUSHING VALVE,
SEE DETAIL, THIS SHEET
3'6"1'9"
1'9"
3'6"
1'9"
MIN. 18" SAND REQUIRED
BELOW STONE TRENCH
INSTALL MIRAFI 140N FILTER
FABRIC OR APPROVED EQUAL
OVER TOP OF STONE BED
1.5"Ø SCH 40 PVC SOLVENT PRIMED AND
WELDED (SEE PRESSURE DISTRIBUTION
SYSTEM DETAILS BELOW)
34" TO 112" WASHED
CRUSHED STONE
MIN. 6" STONE
BELOW PIPE MIN. 12" STONE
BOTTOM OF STONE BED
ELEVATION: 398.5±
12" SOIL COVER OVER ENTIRE MOUND.
TOP 3-4" TO BE TOPSOIL, PLACE SEED,
AND MULCH
EXTEND MOUND SAND 1'
HORIZONTALLY FROM STONE
CUT VEGETATION FLUSH TO GRADE. LEAVE ROOTS IN PLACE
(IF APPLICABLE). PLOW EXISTING GRADE TO A DEPTH OF 7-8".
DO NOT DRIVE CONSTRUCTION EQUIPMENT OVER THE
PLOWED SURFACE UNTIL A MINIMUM 6" LIFT IS INSTALLED.
3
1
2.5' (TYP.)
FLUSHING VALVE BOX
NOT TO SCALE
PRESSURE
DISTRIBUTION
LATERAL
2-45° ELBOWS OR
90° LONG SWEEP
IPS COUPLER
WITH THREADED CAP
PVC OR FIBERGLASS VALVE BOX
WITH REMOVABLE LID
NON-WOVEN
FILTER FABRIC
ABSORPTION
BED/TRENCH
MOUND COVER
FLOW
CLEANOUT
NOT TO SCALE
NOTE:
CLEANOUTS SHALL BE INSTALLED AT A MINIMUM OF EVERY 100' AND AT EACH PIPE JUNCTION
SEWER PIPE
45° OR 22°
ELBOW FITTING
4"Ø SDR 35
PVC RISER PIPE
FINISHED GRADE
INSTALL PVC CLEANOUT ADAPTER AND
THREADED PLUG CAP WITH COILED
WIRE WRAPPED AROUND THE CAP FOR
FUTURE LOCATING PURPOSES.
INSTALL AT OR BELOW FINISHED GRADE.
STANDARD WYE FITTING
DEPTH VARIES
STATE APPROVED MOUND SAND SIEVE SPECIFICATIONS
SIEVE NUMBER
3/8
40
60
100
200
OPENING (MM)
9.5
0.42
0.24
0.149
0.074
% PASSING BY WEIGHT
85-100
25-75
0-30
0-10
0-5
SIEVE NUMBER
4
8
16
30
50
100
OPENING (MM)
4.75
2.38
1.19
0.59
0.297
0.149
% PASSING BY WEIGHT
95-100
80-100
50-80
25-60
10-30
2-10
SIEVE NUMBER
3/8
40
200
OPENING (MM)
9.5
0.42
0.074
% PASSING BY WEIGHT
85-100
30-50
0-5
REFERENCED FROM SECTION 1-921 IN THE VT EPR CHAPTER 1 WASTEWATER SYSTEM
AND POTABLE WATER SUPPLY RULES, EFFECTIVE 4/12/2019
#DATEREVISIONSNOTESSTAMP
DATE: 5/4/2022
SCALE: NTS
PROJECT #: 22-106
DRAWN BY: GWM
CHECKED BY: DAM
APPROVED BY: GWM
5/4/20224-LOT PLANNED UNITDEVELOPMENT47 CHEESEFACTORY ROADSOUTH BURLINGTON, VTHICKORY HILLSIDE, LLC
WASTEWATER
AND WATER
SUPPLY DETAILS
C-2
MOUND SYSTEM INSPECTION
1.The contractor shall notify the designer a minimum of 72
hours prior to construction. If requested, the designer
will provide the layout of the proposed wastewater
disposal trench locations and elevations.
2.The contractor shall provide the designer with a sand
sieve of the proposed mound sand.
3.The designer shall witness the following, prior to
certifying the completion of the system:
3.1.The plowed surface (entire basal area) prior to the
placement of mound sand.
3.2.The force main leakage and pressure test.
3.3.The orifice flow test. Piping must be exposed to
verify 1 psi (minimum) at each orifice.
3.4.The septic tank effluent filter, installed.
3.5.The pretreatment systems installed (if applicable)
3.6.The pump specifications (if an alternate is proposed)
and the pump, installed.
3.7.The pump station floats, and alarm panel installed.
3.8.The finished grading, seeded and mulched.